1 / 1
thumbnail

Description

Active Mature
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 110A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.78 inches wide and 5.51 inches deep. It weighs 4.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Country of Origin
CZ
Part Number
LC1D80008E7
Tariff Code
85364190
EAN
3389110075106
UNSPSC
39121529
Payment methods:
Best offer from:
PLTrusted Automa.Net Supplier
Availability:
2 pcs.
In-Stock
Updated at: 09-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 57 Parts In-Stock from 9 Distributors
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (9)

LC1D80008E7 product image
Schneider Electric

LC1D80008E7

Condition:
New Factory Sealed
Available:
19 pcs.
In-Stock
Updated at: 06-11-2024
Offer from:
USTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1D80008E7 product image
Schneider Electric

LC1D80008E7

Condition:
New Factory Sealed
Available:
10 pcs.
In-Stock
Updated at: 08-11-2024
Offer from:
SKTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1D80008E7 product image
Schneider Electric

LC1D80008E7

Condition:
New Factory Sealed
Available:
6 pcs.
In-Stock
Updated at: 09-11-2024
Offer from:
ITTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1D80008E7 product image
Schneider Electric

LC1D80008E7

Condition:
New Surplus
Available:
4 pcs.
In-Stock
Updated at: 08-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
€339.66
net
LC1D80008E7 product image
Schneider Electric

LC1D80008E7

Condition:
New Surplus
Available:
2 pcs.
In-Stock
Updated at: 21-10-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
15-20 November to United Kingdom
1
£1,349.00
net
Shipping from:
£99.00
Offer with manufacturer lead time
Ships in:On Request
Best price:
€148.42

Environment

Product Certifications
UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
Height
127 mm
Standards
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Climatic Withstand
IACS E10 exposure to damp heat
Net Weight
1.84 kg
Flame Retardance
V1 conforming to UL 94
Protective Treatment
THIEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
96 mm
Depth
140 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C || 60-70 °C with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Power Dissipation Per Pole
12.5 W AC-1
Average Impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current
125 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
0.85...1.1 Uc -40-55 °C operational AC 60 Hz || 0.3...0.6 Uc -40-55 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55 °C operational AC 50 Hz
Mounting Support
plate || rail
Contact Compatibility
M1
Control Circuit Type
AC 50/60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree
3
Rated Breaking Capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Inrush Power In Va
245-245 VA 60 Hz cos phi 0.75 (at 20 °C) || 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947
Pole Contact Composition
2 NO + 2 NC
Connections - Terminals
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end
Coil Technology
without built-in suppressor module
Operating Time
20...35 ms closing || 6...20 ms opening
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability
0.8 Mcycles 125 A AC-1 <= 440 V
Mechanical Durability
4 Mcycles
Compatibility Code
LC1D
Hold-In Power Consumption In Va
26-26 VA 60 Hz cos phi 0.3 (at 20 °C) || 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current
640 A 40 °C - 10 s for power circuit || 990 A 40 °C - 1 s for power circuit || 135 A 40 °C - 10 min for power circuit || 320 A 40 °C - 1 min for power circuit
Heat Dissipation
6-10 W at 50/60 Hz
Protective Cover
without

Specifications

[Uc] Control Circuit Voltage
48 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz
Range Of Product
TeSys Deca
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1
[Ie] Rated Operational Current
125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Poles Description
4P
Device Short Name
LC1D

CAD Models

traceparts
traceparts
Download