Schneider Electric
LC1F1154BD
1 / 1
Description
Active Mature
- Country of Origin
- CZ
- Part Number
- LC1F1154BD
- Tariff Code
- 85364900
- EAN
- 3389118093331
- UNSPSC
- 39121529
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 08-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Specifications
- [Uc] Control Circuit Voltage
- 24 V DC
- Range Of Product
- TeSys F
- [Ue] Rated Operational Voltage
- <= 690 V AC 50/60 Hz || <= 460 V DC
- Contactor Application
- resistive load
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-1
- [Ie] Rated Operational Current
- 200 A 40 °C) <= 440 V AC-1
- Poles Description
- 4P
- Device Short Name
- LC1F
Contractual warranty
- Warranty
- 18 months
Complementary
- Product Certifications
- CCC || ABS || RINA || BV || UL || LROS (Lloyds register of shipping) || CB || RMRoS || DNV || UKCA
- Power Dissipation Per Pole
- 15 W AC-1
- Average Impedance
- 0.37 mOhm - Ith 200 A 50 Hz
- [Ith] Conventional Free Air Thermal Current
- 200 A 40 °C
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc 55 °C) || drop-out 0.15...0.2 Uc 55 °C)
- Standards
- IEC 60947-4-1 || EN 60947-4-1 || IEC 60947-1 || JIS C8201-4-1 || EN 60947-1
- Mounting Support
- plate
- Control Circuit Type
- DC standard
- Hold-In Power Consumption In W
- 4.5-4.5 W 20 °C
- Rated Breaking Capacity
- 920 A IEC 60947-4-1
- Associated Fuse Rating
- 125 A aM <= 440 V || 200 A gG <= 440 V
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Connections - Terminals
- power circuit bar 2 20 x 3 mm || power circuit lugs-ring terminals 1 95-95 mm² || power circuit connector 1 95-95 mm² || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bolted connection
- Pole Contact Composition
- 4 NO
- Operating Time
- 30...40 ms closing || 30...50 ms opening
- Maximum Operating Rate
- 2400 cyc/h 55 °C
- Mechanical Durability
- 10 Mcycles
- Tightening Torque
- power circuit 10 N.m || control circuit 1.2 N.m
- Inrush Power In W
- 560-560 W 20 °C)
- Compatibility Code
- LC1F
- Overvoltage Category
- III
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
- [Icw] Rated Short-Time Withstand Current
- 1100 A 40 °C - 10 s || 640 A 40 °C - 30 s || 520 A 40 °C - 1 min || 400 A 40 °C - 3 min || 320 A 40 °C - 10 min
- Heat Dissipation
- 4.5-4.5 W
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP111201EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI111214EN_V1
- Eu Rohs Directive
- Compliant
Environment
- Ambient Air Temperature For Operation
- -40-60 °C
- Height
- 162 mm
- Net Weight
- 3.83 kg
- Ambient Air Temperature For Storage
- -60-80 °C
- Protective Treatment
- TH
- Ip Degree Of Protection
- IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
- Operating Altitude
- 9842.52 ft (3000 m) without derating
- Width
- 200.5 mm
- Depth
- 171 mm
- Permissible Ambient Air Temperature Around The Device
- 60-70 °C at Uc
CAD Models
traceparts
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther