1 / 1
thumbnail

Description

Active Mature
TeSys F contactor, 3 poles (3NO), 115A/690V AC-3, for motor applications up to 55kW@400V. It provides a 24V 60Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Country of Origin
CZ
Part Number
LC1F115B6
Tariff Code
8536490065
EAN
39121529
UNSPSC
39121529
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 08-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Specifications

[Uc] Control Circuit Voltage
24 V AC 60 Hz
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 690 V AC 50/60 Hz || <= 460 V DC
Contactor Application
resistive load || motor control
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-3 || AC-1
[Ie] Rated Operational Current
200 A 40 °C) <= 440 V AC-1 || 115 A 55 °C) <= 440 V AC-3
Poles Description
3P
Device Short Name
LC1F

Contractual warranty

Warranty
18 months

Complementary

Product Certifications
DNV || CCC || ABS || LROS (Lloyds register of shipping) || UL || RMRoS || CB || BV || RINA || UKCA
Power Dissipation Per Pole
15 W AC-1 || 5 W AC-3
Average Impedance
0.37 mOhm - Ith 200 A 50 Hz
[Ith] Conventional Free Air Thermal Current
200 A 40 °C
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 50/60 Hz 55 °C) || drop-out 0.35...0.55 Uc 50/60 Hz 55 °C)
Standards
IEC 60947-4-1 || IEC 60947-1 || EN 60947-4-1 || EN 60947-1 || JIS C8201-4-1
Mounting Support
plate
Control Circuit Type
AC 60 Hz
Rated Breaking Capacity
920 A IEC 60947-4-1
Associated Fuse Rating
125 A aM <= 440 V || 200 A gG <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
660-660 VA, 60 Hz 0.3 20 °C)
Connections - Terminals
power circuit bar 2 20 x 3 mm || power circuit lugs-ring terminals 1 95-95 mm² || power circuit connector 1 95-95 mm² || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end
Pole Contact Composition
3 NO
Operating Time
23...35 ms closing || 5...15 ms opening
Maximum Operating Rate
2400 cyc/h 55 °C
Mechanical Durability
10 Mcycles
Tightening Torque
power circuit 10 N.m || control circuit 1.2 N.m
Compatibility Code
LC1F
Hold-In Power Consumption In Va
55-55 VA, 60 Hz 0.3 20 °C)
Overvoltage Category
III
Motor Power Kw
55 kW 380...400 V AC 50/60 Hz AC-3) || 59 kW 415 V AC 50/60 Hz AC-3) || 59 kW 440 V AC 50/60 Hz AC-3) || 75 kW 500 V AC 50/60 Hz AC-3) || 80 kW 660...690 V AC 50/60 Hz AC-3) || 30 kW 220...230 V AC 50/60 Hz AC-3) || 18.5 kW 400 V AC 50/60 Hz AC-4)
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
1100 A 40 °C - 10 s || 640 A 40 °C - 30 s || 520 A 40 °C - 1 min || 400 A 40 °C - 3 min || 320 A 40 °C - 10 min
Heat Dissipation
12-16 W

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP111201EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI111214EN_V1
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-40-60 °C
Height
162 mm
Net Weight
3.43 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Width
163.3 mm
Depth
171 mm
Permissible Ambient Air Temperature Around The Device
60-70 °C at Uc

CAD Models

traceparts
traceparts
Download