- Product Certifications
- BV || DNV || CB || RINA || CSA || UL || LROS (Lloyds register of shipping) || ABS || RMRoS || UKCA
- Power Dissipation Per Pole
- 120 W AC-1 || 48 W AC-3
- Average Impedance
- 0.12 mOhm - Ith 1000 A 50 Hz
- [Ith] Conventional Free Air Thermal Current
- 1000 A 40 °C || 1250 A
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.25...0.5 Uc 40...400 Hz 55 °C)
- Standards
- IEC 60947-4-1 || JIS C8201-4-1 || EN 60947-4-1 || EN 60947-1 || IEC 60947-1
- Mounting Support
- plate
- Control Circuit Type
- AC 40...400 Hz
- Contactor Coil Voltage
- 115 V AC standard
- Rated Breaking Capacity
- 5040 A IEC 60947-4-1
- Power Range
- 250-500 kW 380-440 V 3 phase || 110-220 kW 200-240 V 3 phase || 250-500 kW 480-500 V 3 phase
- Associated Fuse Rating
- 1000 A gG <= 440 V || 630 A aM <= 440 V
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 1650-1650 VA, 40...400 Hz 0.9 20 °C)
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 60 x 5 mm || power circuit bolted connection
- Pole Contact Composition
- 3 NO
- Motor Starter Type
- direct on-line contactor
- Operating Time
- 40...80 ms closing || 100...200 ms opening
- Maximum Operating Rate
- 1200 cyc/h 55 °C
- Mechanical Durability
- 5 Mcycles
- Tightening Torque
- control circuit 1.2 N.m || power circuit 58 N.m
- Compatibility Code
- LC1F
- Hold-In Power Consumption In Va
- 22-22 VA, 40...400 Hz 0.9 20 °C)
- Overvoltage Category
- III
- Motor Power Kw
- 335 kW 380...400 V AC 50/60 Hz AC-3) || 375 kW 415 V AC 50/60 Hz AC-3) || 400 kW 440 V AC 50/60 Hz AC-3) || 400 kW 500 V AC 50/60 Hz AC-3) || 450 kW 660...690 V AC 50/60 Hz AC-3) || 450 kW 1000 V AC 50/60 Hz AC-3) || 200 kW 220...230 V AC 50/60 Hz AC-3) || 100 kW 400 V AC 50/60 Hz AC-4)
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
- [Icw] Rated Short-Time Withstand Current
- 5050 A 40 °C - 10 s || 4400 A 40 °C - 30 s || 3400 A 40 °C - 1 min || 2200 A 40 °C - 3 min || 1600 A 40 °C - 10 min
- Heat Dissipation
- 20-20 W