Schneider Electric
LC1G630EHEN
1 / 1
Description
Active Mature
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 630A 400kW@440V. It provides a 48-130V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 324mm x 210mm x 248mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.- Part Number
- LC1G630EHEN
- Tariff Code
- 8536490065
- EAN
- 39121529
- UNSPSC
- 39121529
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Complementary
- Product Certifications
- CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
- Height
- 284 mm
- Power Dissipation Per Pole
- 70 W AC-1 - Ith 1050 A || 26 W AC-3 - Ith 630 A
- Average Impedance
- 0.000065 Ohm
- Auxiliary Contact Composition
- 1 NO + 1 NC
- Connection Pitch
- 70 mm
- [Ith] Conventional Free Air Thermal Current
- 1050 A (at 40 °C)
- Standards
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1
- Mounting Support
- plate
- Hold-In Power Consumption In W
- 9.5-9.5 W
- Rated Breaking Capacity
- 5550 A at 440 V
- Irms Rated Making Capacity
- 7220 A at 440 V
- Associated Fuse Rating
- 630 A aM at <= 440 V for motor || 500 A aM at <= 690 V for motor || 1250 A gG at <= 690 V
- Net Weight
- 14.2 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 990-990 VA
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- power circuit: bar 2 - busbar cross section: 52 x 20 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end
- Coil Technology
- built-in bidirectional peak limiting
- Operating Time
- 40...70 ms closing || 15...50 ms opening
- Maximum Operating Rate
- 600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
- Mechanical Durability
- 5 Mcycles
- Tightening Torque
- 58 N.m
- Compatibility Code
- LC1G
- Hold-In Power Consumption In Va
- 18.7-18.7 VA
- Width
- 211 mm
- Overvoltage Category
- III
- Depth
- 266 mm
- Maximum Horse Power Rating
- 250 hp at 200/208 V 60 Hz || 300 hp at 230/240 V 60 Hz || 600 hp at 460/480 V 60 Hz || 700 hp at 575/600 V 60 Hz
- Motor Power Kw
- 180 kW at 230 V AC 50/60 Hz (AC-3e) || 315 kW at 400 V AC 50/60 Hz (AC-3e) || 335 kW at 415 V AC 50/60 Hz (AC-3e) || 355 kW at 440 V AC 50/60 Hz (AC-3e) || 375 kW at 500 V AC 50/60 Hz (AC-3e) || 500 kW at 690 V AC 50/60 Hz (AC-3e) || 450 kW at 1000 V AC 50/60 Hz (AC-3e) || 200 kW at 230 V AC 50/60 Hz (AC-3) || 335 kW at 400 V AC 50/60 Hz (AC-3) || 375 kW at 415 V AC 50/60 Hz (AC-3) || 400 kW at 440 V AC 50/60 Hz (AC-3) || 400 kW at 500 V AC 50/60 Hz (AC-3) || 500 kW at 690 V AC 50/60 Hz (AC-3) || 450 kW at 1000 V AC 50/60 Hz (AC-3) || 180 kW at 230 V AC 50/60 Hz (AC-4) || 315 kW at 400 V AC 50/60 Hz (AC-4) || 335 kW at 415 V AC 50/60 Hz (AC-4) || 355 kW at 440 V AC 50/60 Hz (AC-4) || 375 kW at 500 V AC 50/60 Hz (AC-4) || 450 kW at 690 V AC 50/60 Hz (AC-4) || 355 kW at 1000 V AC 50/60 Hz (AC-4)
- [Ui] Rated Insulation Voltage
- 1000 V
- Inrush Power In W
- 790 W
- [Icw] Rated Short-Time Withstand Current
- 5.05 kA - 10 s || 4.4 kA - 30 s || 3.4 kA - 1 min || 2.2 kA - 3 min || 1.6 kA - 10 min
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2105013
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI2105013
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free plastic parts product
Specifications
- [Uc] Control Circuit Voltage
- 48...130 V AC 50/60 Hz || 48...130 V DC
- [Ue] Rated Operational Voltage
- <= 1000 V AC 50/60 Hz || <= 460 V DC
- Range Of Product
- TeSys Giga
- Control Circuit Voltage Limits
- operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
- Contactor Application
- power switching || motor control
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
- [Ie] Rated Operational Current
- 1050 A (at <40 °C) at <= 1000 V AC-1 || 630 A (at <60 °C) at <= 440 V AC-3
- Poles Description
- 3P
- Device Short Name
- LC1G
Environment
- Ambient Air Temperature For Operation
- -25-60 °C
- Ambient Air Temperature For Storage
- -60-80 °C
- Protective Treatment
- TH
- Ip Degree Of Protection
- IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
- Mechanical Robustness
- vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
- Color
- dark grey
- Permissible Ambient Air Temperature Around The Device
- -40-70 °C at Uc
Documents
Data Sheet
DownloadCAD Models
traceparts
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther