Environment

Mechanical Robustness
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Ambient Air Temperature For Operation
-25-50 °C
Height
58 mm
Net Weight
0.38 kg
Flame Retardance
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage
-50-80 °C
Protective Treatment
TC IEC 60068 || TC DIN 50016
Ip Degree Of Protection
IP20 VDE 0106
Operating Altitude
6561.68 ft (2000 m) without derating
Width
90 mm
Depth
57 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503003EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1503003EN
Eu Rohs Directive
Compliant

Complementary

Control Circuit Voltage Limits
operational: 0.8...1.15 Uc (at <50 °C) || drop-out: 0.2...0.75 Uc (at <50 °C)
Inrush Power In Va
30-30 VA (at 20 °C)
Hold-In Power Consumption In Va
4.5-4.5 VA (at 20 °C)
Heat Dissipation
1.3-1.3 W

Specifications

Product Certifications
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Interlocking Type
mechanical
[Uc] Control Circuit Voltage
48 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit 690 V AC 50/60 Hz
Average Impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current
20 A (at 60 °C) for power circuit
Standards
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Mounting Support
plate || rail
Control Circuit Type
AC 50/60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
resistive load
Rated Breaking Capacity
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
Product Or Component Type
changeover contactor
Irms Rated Making Capacity
110 A AC for power circuit conforming to IEC 60947
Product Name
TeSys K
Associated Fuse Rating
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end
Range
TeSys
Pole Contact Composition
4 NO
Device Presentation
preassembled with reversing power busbar
Utilisation Category
AC-1
[Ie] Rated Operational Current
20 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Maximum Operating Rate
3600 cyc/h
Electrical Durability
0.16 Mcycles 20 A AC-1 <= 690 V
Mechanical Durability
5 Mcycles
Poles Description
4P
Operating Time
10...20 ms coil energisation and NO closing || 10...20 ms coil de-energisation and NO opening
Tightening Torque
0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA C22.2 No 14
Device Application
control
Device Short Name
LC2K
[Icw] Rated Short-Time Withstand Current
90 A 50 °C - 1 s for power circuit || 85 A 50 °C - 5 s for power circuit || 80 A 50 °C - 10 s for power circuit || 60 A 50 °C - 30 s for power circuit || 45 A 50 °C - 1 min for power circuit || 40 A 50 °C - 3 min for power circuit || 20 A 50 °C - >= 15 min for power circuit

CAD Models

traceparts
traceparts
Download