Schneider Electric
LJL36600U33X
1 / 1
Description
Active Mature
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 600A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.- Country of Origin
- US
- Part Number
- LJL36600U33X
- Tariff Code
- 8536200020
- EAN
- 39121601
- UPC
- 785901976301
- UNSPSC
- 39121601
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Environment
- Ambient Air Temperature For Operation
- -2-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications
- UL || CSA || NOM
- Ip Degree Of Protection
- front cover IP40
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206029EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206029EN
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL600LS52K3
- [Ics] Rated Service Breaking Capacity
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Technology
- electronic, standard, MicroLogic 3.3 S, LSI
- Trip Unit Name
- MicroLogic 3.3 S
- Height
- 340 mm
- [Ue] Rated Operational Voltage
- 600 V AC 50/60 Hz IEC 60947-3
- Tightening Torque
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Mounting Support
- lug
- Breaking Capacity Code
- J
- Local Signalling
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- lugs, line || lugs, load
- Net Weight
- 6.2 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 31 mm || 61 mm
- Line Rated Current
- 600-600 A
- Utilisation Category
- category A
- Long Time Pick-Up Adjustment Range
- 0.25...1 x In
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-2
- Communication Interface
- Modbus || Ethernet
- Poles Description
- 3P
- Awg Gauge
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Color
- Black
- Width
- 140 mm
- Depth
- 110 mm
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact L
- Range
- PowerPact
- Device Application
- distribution
- Device Short Name
- L-Frame
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther