1 / 1
thumbnail

Description

Active Mature
LR9D5569 is a TeSys LR9D electronic overload relay from Schneider Electric to be used with a TeSys D contactor. With a thermal range 90-150A, a tripping class 20 and phase unbalance protection, it protects motors 55 to 75kW@400V. LR9D5569 is a TeSys LR9D electronic overload relay from Schneider Electric to be combined with a TeSys D contactor. With a thermal setting range 90-150A, a tripping class 20 and phase unbalance detection, it protects motors 55 to 75kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection, electronic type, with phase unbalance protection (differential), self powered (no external power supply needed). To be combined with Tesys LC1D115-D150 contactors. Light and compact, 120mm wide. Manual control with test & reset buttons, manual / automatic reset selector. High accuracy, temperature compensated to keep a precise tripping over the ambient temperature range. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. 90% reduction in energy dissipation compared to a thermal overload relay.
Country of Origin
FR
Part Number
LR9D5569
Tariff Code
85364900
EAN
3389110787948
UNSPSC
39122330
Payment methods:
Best offer from:
SKTrusted Automa.Net Supplier
Availability:
10 pcs.
In-Stock
Updated at: 08-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 12 Parts In-Stock from 3 Distributors
Delivery from:
SK
SK
GB
GB
DE
DE
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (2)

LR9D5569 product image
Schneider Electric

LR9D5569

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 21-10-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
1
LR9D5569 product image
Schneider Electric

LR9D5569

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 08-11-2024
Offer from:
DETrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
€157.16

Environment

Product Certifications
UL || CSA || CCC || UKCA
Mechanical Robustness
vibrations2 Gn, 5...300 Hz IEC 60068-2-6 || shocks13 Gn for 11 ms IEC 60068-2-7
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
Climatic Withstand
IACS E10
Ambient Air Temperature For Operation
-20-60 °C without derating IEC 60947-4-1
Dielectric Strength
1.89 kV 50 Hz IEC 60947-1
Ip Degree Of Protection
IP20 conforming to IEC 60529
Ambient Air Temperature For Storage
-60-70 °C
Operating Altitude
<= 6561.68 ft (2000 m) without derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2212018
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2212018
Eu Rohs Directive
Compliant with Exemptions

Complementary

Network Frequency
50-60 Hz
Height
118 mm
[Ith] Conventional Free Air Thermal Current
5 A signalling circuit
Auxiliary Contact Composition
1 NO + 1 NC
Connections - Terminals
power circuit bars || control circuit screw clamp terminals 1 0.5-1.5 mm² flexible without cable end || control circuit screw clamp terminals 2 0.5-1.5 mm² flexible without cable end || alarm circuit screw clamp terminals 1 0.5-1.5 mm² flexible without cable end
Phase Failure Sensitivity
tripping in 4 s +/- 20 % IEC 60947-4-1
[Ue] Rated Operational Voltage
690 V AC 0...400 Hz power circuit IEC 60947-4-1
Switching Capacity In Ma
0...150 mA
Associated Fuse Rating
4 A gG for signalling circuit || 4 A BS for signalling circuit
Net Weight
0.885 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-1
Maximum Voltage Drop
<2.5 V closed state
Supply Voltage Limits
17-32 V
Tripping Threshold
1.05 +/- 0.06 In alarm IEC 60947-4-1 || 1.12 +/- 0.06 In de-energisation IEC 60947-4-1
Tightening Torque
alarm circuit 0.45 N.m screw clamp terminals || power circuit 18 N.m bars M8 || control circuit 1.2 N.m screw clamp terminals
Control Type
Red push-button stop || Blue push-button reset
Mounting Support
under contactor || rail
Width
115 mm
Depth
125 mm
[Us] Rated Supply Voltage
24 V DC
Temperature Compensation
-20-60 °C

Specifications

Signalling Function
alarm
Network Type
AC
Thermal Protection Adjustment Range
90-150 A
Relay Application
motor protection
Product Or Component Type
electronic thermal overload relay
Product Name
TeSys LRD || TeSys Deca
Thermal Overload Class
class 20 IEC 60947-4-1
Range
TeSys
[Ui] Rated Insulation Voltage
power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
Product Compatibility
NSX circuit breaker || LC1D115 || LC1D150
Device Short Name
LR9D

CAD Models

traceparts
traceparts
Download