1 / 1
thumbnail

Description

Active Mature
It is a 48-130V AC/DC control module for 3 poles TeSys Giga 265-300 contactor (advanced version). Coil designed for less energy consumption and wider voltage band-width, connection by spring terminal. It allows contactor operation with high AC-3 operating rates until 600 cycles/hour and environments until 60°C. Control module has connectors for connecting the coil control A1, A2 circuit, pole status and diagnostic signaling circuits. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It is accessible from the front and maintained with very low down times. Unique QR code provides quick access to complete product data.
Country of Origin
CN
Part Number
LX1G3REHEN
Tariff Code
85059090
EAN
3606481946300
UNSPSC
39121010
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

[Uc] Control Circuit Voltage
48...130 V AC/DC 50/60 Hz
Range Compatibility
TeSys G LX1G contactor coil
Product Or Component Type
contactor coil
Range
TeSys
Maximum Operating Rate
600 cyc/mn 60 °C
Poles Description
3P
Operating Time
20...35 ms opening || 40...55 ms closing
Product Compatibility
LC1G265...330
Device Short Name
LX1G
Mechanical Durability
5 Mcycles

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2105013
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI2105013
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Control Circuit Voltage Limits
operational 0.8...1.1 Uc 60 °C) || drop-out 0...0.45 Uc 60 °C)
Hold-In Power Consumption In W
4.5-4.5 W DC
Inrush Power In Va
965-965 VA 120 V AC, 60 Hz
Connections - Terminals
control circuit push-in termination 1 0.2-2.5 mm² solid stranded without cable end sleeve AWG 26...AWG 12 || control circuit push-in termination 1 0.25-2.5 mm² flexible with cable end sleeve AWG 24...AWG 14 || control circuit push-in termination 2 0.5-1.0 mm² rigid or stranded with cable end sleeve AWG 20...AWG 18
Coil Technology
built-in bidirectional peak limiting
Hold-In Power Consumption In Va
16-16 VA 120 V AC, 60 Hz
Inrush Power In W
695.0 W DC

Environment

Ambient Air Temperature For Operation
-25-60 °C
Height
167.0 mm
Standards
EN/IEC 60947-4-1 || UL 60947-4-1A || CSA C22.2 No 60947-4-1
Electromagnetic Compatibility
EMC immunity conforming to IEC 60947-4-1 || emission tests criteria A conforming to IEC 60947-4-1 || immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3 || voltage dips and interruptions immunity test conforming to SEMI F47
Ip Degree Of Protection
IP20 IEC 60529
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-60-80 °C
Operating Altitude
9842.52 ft (3000 m) without derating || 5000 m with derating factor
Quantity Per Set
1
Width
140.0 mm
Depth
93.0 mm
Permissible Ambient Air Temperature Around The Device
-40-70 °C at Uc

CAD Models

traceparts
traceparts
Download

Other Categories