Schneider Electric

METSEION7403

1 / 1
thumbnail

Description

Active Mature
PowerLogic ION7400 utility feeder power meters combine capabilities not typically available in compact meters. They offers a hight flexibility and usability, along with accurate 3-phase energy and power measurements with data logging. Use Power Monitoring Expert software for data analysis or share operation data with SCADA systems through multiple communication channels and protocols. Certified by third party labs for energy accuracy (IEC 62052-11, IEC 62052-22, IEC 62052-24) and power quality (IEC 62586-2, IEC 61000-4-30 Class S). Cybersecurity features include secure protocols (HTTPS, SFTP), security event logging, Syslog protocol. Ability to enable/disable communication ports, and 16 user configurable accounts. With 512 MB of memory to support 50 data logs, 50+ user-definable alarms, waveform captures, 1/2 cycle RMS logging, custom web pages, min/max logs, energy trends, and Time of Use. The ability to timestamp events to +/-1 ms utilizing time synchronization method that include PTP (IEEE1588), NTP, IRIG-B, GPS ASCII (RS485) and network time set function. 3 digital inputs and one digital output. I/O option modules include 2 relays and 6 digital inputs or 2 analog outputs and 4 analog inputs. Wide control power range of 90-415 VAC / 110-415 VDC. Operating environment of -25 to +70C; Humidity rating of 5% to 95%; Altitude up to 3000 m. DIN rail mounting (no display).
Country of Origin
CA
Part Number
METSEION7403
Tariff Code
90308400
EAN
3606480930614
UNSPSC
83101808
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Complementary

Communication Network Type
IPv6 (internet protocol)
Network Frequency
50 Hz || 60 Hz
Communication Port Support
ETHERNET || screw terminal block RS485 || mini B USB USB
Power Quality Analysis
EN 50160 2010 compliance report || IEEE 519 2014 compliance report || IEC 61000-4-30 class S power quality measurement || up to the 63rd harmonic || harmonic distortion || waveform capture || voltage sag and swell detection || programmablity (logic and math functions) || IEC 62586 power quality monitoring || IEC 61000-4-15 disturbance direction detection || rapid voltage change
Height
90.5 mm
Measurement Voltage
57-400 V AC 42...69 Hz between phase and neutral || 100-690 V AC 42...69 Hz between phases
Sampling Rate
256 samples/cycle
Standards
IEC 62052-11 || IEC 61557-12 || IEC 62053-22 || IEC 62053-24 || IEC 61326-1 || IEEE 1588 || IEC 62586
Memory Capacity
512 MB
Number Of Outputs
1 pulse
Product Certifications
CE || cULus || N998
Type Of Measurement
current || voltage || frequency || active and reactive power total || apparent power total || power factor total || active and reactive power per phase, rms || apparent power per phase, rms || power factor per phase, rms || active and reactive energy || apparent energy
Communication Port Protocol
Modbus RTU 115 kbauds - 2-wire || ION 115 kbauds - 2-wire || DNP3 || IEC 61850 || Modbus TCP/IP || Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s || RSTP 801.1d 2004 || DLMS
Frequency Measurement Range
42-69 Hz
Communication Service
SMTP e-mail notification || NTP time synchronization || RSTP support || DHCP || PTP time synchronization
Power Consumption In Va
18 VA 415 V AC
Number Of Inputs
3 digital 30 V AC || 3 digital 60 V DC
Net Weight
528 g
Type Of Installation
indoor installation
Depth
90.8 mm
Measurement Current
50-10000 mA
Information Displayed
voltage || current || frequency || power || energy consumption || harmonic distortion
[Us] Rated Supply Voltage
90...415 V AC 45...65 Hz +/- 10 % || 110...415 V DC +/- 10 %
Mounting Mode
clip-on
Measurement Accuracy
current +/- 0.1 % || voltage +/- 0.1 % || active energy +/- 0.2 %
Mounting Support
DIN rail
Poles Description
3P + N || 3P || 1P + N
Data Recording
time stamping || trending/forecasting || waveform logs || sequence of event recording || min/max of instantaneous values || harmonics logs || data logs || sag and swell logs || GPS synchronisation || event logs || alarm logs || 50 data recorders
Line Rated Current
1 A || 5 A || 10 A
Cybersecurity
enable/disable communication ports || port hardening || Syslog protocol support || password protection || robust security logs
Isolation Voltage
III400-690 V conforming to IEC 61010-1:ed. 3 || III400-690 V conforming to EN 61010-1:ed. 3 || III347-600 V conforming to UL 61010-1:ed. 3 || III347-600 V conforming to CSA C22.2 No 61010-1:ed. 3
Analogue Input Type
voltage (impedance 5 MOhm) || current (impedance 0.3 mOhm)
Web Services
customizable home page || file upload/download via FTP || file upload/download via SFTP || web server || alarm notification by e-mail || viewing of captured waveform (FTP) || viewing of captured waveform (web) || HTTPS server
Width
90.5 mm
Display Type
Without Display
Device Application
revenue billing || data aggregation || power monitoring || WAGES metering
Accuracy Class
class 0.2S active energy IEC 62053-22 || class 0.2 active energy ANSI C12.20 || class 0.2 active power IEC 61557-12 || class 0.5S reactive energy IEC 62053-24 || class 0.5 power factor IEC 61557-12 || class 0.2 voltage IEC 61557-12 || class 0.2 current IEC 61557-12 || class 0.2 frequency IEC 61557-12 || class 0.2 active energy IEC 61557-12
Installation Category
III

Offer Sustainability

Rohs Exemption Information
Yes
Environmental Disclosure
ENVPEP1512006EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1512006EN
Eu Rohs Directive
Compliant with Exemptions

Environment

Ambient Air Temperature For Operation
-25-70 °C
Electromagnetic Compatibility
electrostatic discharge conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test conforming to IEC 61000-4-4 || surge immunity test conforming to IEC 61000-4-5 || conducted RF disturbances conforming to IEC 61000-4-6 || magnetic field at power frequency conforming to IEC 61000-4-8 || voltage dips and interruptions immunity test conforming to IEC 61000-4-11 || immunity to impulse waves conforming to IEC 61000-4-12 || conducted and radiated emissions conforming to EN 55022 || conducted and radiated emissions conforming to EN 55011 || conducted and radiated emissions conforming to FCC part 15 || conducted and radiated emissions conforming to ICES-003 || conducted RF disturbances (2...150 Hz) conforming to CLC/TR 50579 || surge withstand conforming to IEEE C37.90.1
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
5-95 %
Ip Degree Of Protection
IP30 IEC 60529
Operating Altitude
9842.52 ft (3000 m)

Specifications

Product Or Component Type
power meter
Product Name
PowerLogic ION7400
Range
PowerLogic
Device Short Name
ION7403