Schneider Electric
PJA36000S60
1 / 1
Description
Active Mature
PowerPacT P-Frame automatic switches are a disconnect device and can be used to open and close a circuit under normal operating conditions. The automatic switches are similar in construction, use the same accessories, and offer the same connection possibilities as the P-Frame circuit breaker version. The switches have a factory set, nonadjustable trip point calibrated to protect the molded case switch. The automatic switch can make and break its rated current. For an overload or a short circuit, it must be protected by an upstream device. PowerPacT P-Frame switches are available in unit mount, I-Line, plug-in, or drawout versions. This switch has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT P, 600A, 3 pole, automatic switch has a short circuit withstand current rating of 25kA at 600VAC. It has an ABC phase connection. PowerPacT P automatic switches comply to UL and CSA standards.- Country of Origin
- US
- Part Number
- PJA36000S60
- Tariff Code
- 8536200020
- UNSPSC
- 39121601
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Environment
- Product Certifications
- CSA || UL Listed || IEC
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206033EN
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206033EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Eu Rohs Directive
- Compliant with Exemptions
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Complementary
- Terminal Identifier
- AL800M23K
- Height
- 16.24 in
- Mounting Mode
- I-Line
- Short-Circuit Withstand
- 65 kA 480 V UL 489 || 25 kA 600 V UL 489 || 100 kA 240 V UL 489
- Tightening Torque
- 50-50 N.m 95-240 mm² (AWG 3/0...500 kcmil)
- Breaking Capacity Code
- J
- Magnetic Tripping Current
- 10000-10000 A
- Poles Description
- 3P
- Line Rated Current
- 600 A
- Width
- 16.54 in
- Electrical Connection
- lugs, load || I-Line connection, line
- Depth
- 14.49 in
- [Ue] Rated Operational Voltage
- 600 V AC
- Awg Gauge
- 3 x AWG 3/0...500 kcmil ( aluminium/copper )
Specifications
- Range Of Product
- PowerPact P
- Product Or Component Type
- automatic switch
- Trip Unit Technology
- magnetic
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther