- Output Voltage
- 240 V 5 A AC-12 || 30 V 2 A DC-13 || 240 V 1.5 A AC-15
- Power Consumption In W
- 0.5 W 24 V || 1.7 W 240 V
- Setting Accuracy Of Time Delay
- +/- 5 % of full scale 25 °C IEC 61812-1
- Control Type
- selector switch front panel
- Mounting Support
- base mounted: socket || panel mounted: system supplied with the product
- Temperature Drift
- +/- 0.02 %/°C of the maximum setting value IEC 61812-1
- Pick Up Duration
- 55 ms
- Maximum Switching Current
- 5 A
- Marking
- CE
- Product Front Plate Size
- 48 x 48 mm
- Net Weight
- 0.14 kg
- Minimum Pulse Duration
- 20 ms
- Reset Time
- 25 ms on de-energisation
- Power Consumption In Va
- 1.1 VA 24 V || 4.8 VA 240 V
- Maximum Switching Voltage
- 250 V AC/DC
- Surge Withstand
- 1 kV differential mode IEC 61000-4-5 level 3 || 2 kV common mode IEC 61000-4-5 level 3
- Voltage Drift
- +/- 0.2 %/V of the maximum setting value 48...240 V || +/- 1 %/V of the maximum setting value 24...48 V
- Electrical Durability
- 100000 cycles
- Minimum Switching Current
- 100 mA
- Local Signalling
- for output relay state 1 LED (yellow) || for flashing: relay energised timing in progress LED indicator (green) || for on steady: relay energised, no timing in progress LED indicator (green)
- Mechanical Durability
- 30000000 cycles
- On-Load Factor
- 100 %
- Housing Material
- self-extinguishing
- Breaking Capacity
- 1250 VA
- Repeat Accuracy
- +/- 0.2 % of the maximum setting value IEC 61812-1