- [Us] Rated Supply Voltage
- 110...240 V AC/DC 50/60 Hz +/- 10 %
- Safety Reliability Data
- B10d = 470000 || MTTFd = 502.2 years
- Maximum Measuring Cycle
- 150 ms measurement cycle as true rms value
- Hysteresis
- 3-3 % fixed threshold setting
- Insulation Resistance
- > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
- Measurement Error
- < 1 % over the whole range with voltage variation || 0.2 %/°C with temperature variation
- Operating Rate
- <= 360 operations/hour full load
- Output Contacts
- 1 C/O
- Immunity To Microbreaks
- 20 ms
- Polarity
- non reversible polarity on DC supply
- Operating Position
- any position without derating
- Net Weight
- 0.08 kg
- Maximum Switching Voltage
- 250 V AC/DC
- Reset Time
- 1500 ms time delay
- Run-Up Delay At Power-Up
- 1000 ms DC || 500 ms AC
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- Functionality
- overvoltage and undervoltage detection
- [Ui] Rated Insulation Voltage
- 250 V IEC 60664-1 || 400 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Quality Labels
- CE
- Supply Voltage Limits
- 50-270 V AC/DC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for power ON LED (green) || for relay ON LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Compatibility Code
- RM17
- Housing Material
- self-extinguishing plastic
- Control Circuit Frequency
- 50...60 Hz +/- 10 %
- Measurement Accuracy
- +/- 10 % of the full scale value
- Width
- 17.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 1 W DC
- Electrical Durability
- 100000 cycles
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit || +/- 1 % time delay