- [Us] Rated Supply Voltage
- 24...240 V AC/DC 50/60 Hz
- Safety Reliability Data
- MTTFd = 308.2 years || B10d = 290000
- Maximum Measuring Cycle
- 100 ms measurement cycle as true rms value
- Hysteresis
- 3-3 % fixed full scale for window mode || 5-50 % adjustable threshold setting
- Insulation Resistance
- > 100 MOhm 500 V DC
- Measurement Error
- < 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation
- Output Contacts
- 2 C/O
- Contacts Material
- cadmium free
- Immunity To Microbreaks
- 10 ms
- Response Time
- <= 500 ms
- Net Weight
- 0.11 kg
- Maximum Switching Voltage
- 250 V AC
- Reset Time
- 1500 ms at maximum voltage
- Run-Up Delay At Power-Up
- 600 ms
- Connections - Terminals
- screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
- Functionality
- undervoltage and overvoltage in window mode
- Overvoltage Category
- III IEC 60664-1
- Insulation
- between supply and measurement
- Supply Voltage Limits
- 20.4-264 V AC/DC
- Mounting Support
- 35 mm DIN rail conforming to IEC 60715
- Nominal Output Current
- 8 A
- Mechanical Durability
- 10000000 cycles
- Compatibility Code
- RM22
- Housing Material
- self-extinguishing plastic
- Resistance Across Terminals
- 30 kOhm E2-M terminals || 5 kOhm E1-M terminals || 50 kOhm E3-M terminals
- Width
- 22.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 1.5 W DC
- Electrical Durability
- 100000 cycles
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit || +/- 2 % time delay