- [Us] Rated Supply Voltage
- 24...240 V AC/DC 50/60 Hz +/- 10 %
- Safety Reliability Data
- B10d = 170000 || MTTFd = 182.6 years
- Control Circuit Voltage Limits
- 15 % + 10 % Un
- Cable Capacitance
- 1 nF HS (High Sensitivity) probe cable || 2.2 nF St (Standard Sensitivity) probe cable || 4.7 nF LS (Low Sensitivity)
- Insulation Resistance
- > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 || > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 || > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
- Measurement Error
- 0.5 %/°C with temperature variation
- Operating Rate
- <= 360 operations/hour full load
- Output Contacts
- 2 C/O
- Reset Time
- 1750 ms
- Marking
- CE : 73/23/EEC || CE : EMC 89/336/EEC
- Operating Position
- any position without derating
- Sensitivity Scale
- 0.25...5 kOhm LS (Low Sensitivity) || 5...100 kOhm St (Standard Sensitivity) || 50...1000 kOhm HS (High Sensitivity)
- Maximum Switching Voltage
- 250 V AC/DC
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
- [Ui] Rated Insulation Voltage
- 250 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 20.4-264 V AC/DC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for relay ON LED (yellow) || for power ON LED (green) || for timer ON LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Maximum Supply Current For Sensors
- 1 mA
- Housing Material
- self-extinguishing plastic
- Measurement Accuracy
- +/- 10 % of the full scale value || +/- 20 % for the HS range
- Width
- 35 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 1.5 W DC
- Sensitivity Adjustment
- 5-100 %
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 0.6 s
- Repeat Accuracy
- +/- 2 % time delay