Schneider Electric

S8650C0C0E6E1A0A

1 / 1
thumbnail

Description

Active Mature
Part Number
S8650C0C0E6E1A0A
Tariff Code
9028300000
EAN
39121106
UNSPSC
39121106
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Product Or Component Type
energy and power quality meter
Product Name
PowerLogic ION8650
Range
PowerLogic
Device Short Name
ION8650C

Complementary

Network Frequency
60 Hz
Communication Port Support
RJ45 ETHERNET || SUB-D 9 RS485/RS232 || infrared || terminal block RS485
Power Quality Analysis
harmonic distortion || programmablity (logic and math functions) || voltage sag and swell detection || up to the 31st harmonic
Measurement Voltage
57-277 V AC phase to neutral || 100-480 V AC phase to phase
Sampling Rate
1024 samples/cycle
Memory Capacity
32 MB
Number Of Outputs
2 pulse
Type Of Measurement
power factor total || power factor per phase || apparent power total || apparent power per phase || active power total || active power per phase || reactive power total || reactive power per phase || current || voltage || frequency
Communication Port Protocol
TCP/IP 10/100 Mbit/s || DNP3 300...115200 bauds || ION 300...115200 bauds || DLMS 300...115200 bauds || Modbus 57600 bauds || Ansi C12.18 <= 19200 bauds || DNP3 10/100 Mbit/s || ION 10/100 Mbit/s || IEC 61850 ed. 2 10/100 Mbit/s || EtherGate || Modbus RTU, slave 300...115200 bauds || Modbus TCP, slave 10/100 Mbit/s
Power Consumption In Va
24 VA
Number Of Inputs
0
Tamperproof Of Settings
protected by access code
Measurement Current
0.001-24 A
Form Designation
9S 3-element 4 || 36S 2 1/2-element 4 || 29S 2 1/2-element 4
Time Synchronisation Protocol
GPS: Truetime/Datum || IRIG-B
Measurement Accuracy
current 0.1 % || voltage 0.1 % || power 0.1 % || power factor 0.1 % || frequency 0.001 Hz || energy 0.1 %
Ethernet Service
SNMP-Traps and SYSLOG || enable/disable Ethernet protocols || enable/disable serial ports
Poles Description
3P || 1P + N || 3P + N
Compatibility Code
ION8650C
Data Recording
revenue logs || GPS synchronisation || event logs || historical logs || data logs || sag and swell logs || harmonics logs || alarms || time stamping
[Us] Rated Supply Voltage
120...277 V AC 47...63 Hz
Line Rated Current
5 A || 2 A || 1 A
Analogue Input Type
current 0.01...20 A 0.05 Ohm)
Web Services
port addressing user designed || robust security logs || web server || alarm notification by e-mail
Display Type
FSTN transflective LCD
Transmission Rate
10/100 Mbit/s || 300...115200 bauds || 57600 bauds || <= 19200 bauds
Device Application
load curtailment || demand and power factor control || equipment monitoring and control || instrument transformer correction || co-generation and IPP monitoring || tariff metering || energy pulsing and totalisation
Accuracy Class
class 0.2S energy IEC 62053-22 || class 0.2S energy IEC 62053-23 || class 0.2 energy ANSI C12.20
Maximum Power Consumption In Va
33 VA

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110723EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI110703EN
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-40-85 °C
Height
178 mm
Standards
ANSI C12.1 || IEC 62052-11
Electromagnetic Compatibility
electrostatic discharge immunity test IEC 61000-4-2 || susceptibility to electromagnetic fields IEC 61000-4-3 || electrical fast transient/burst immunity test IEC 61000-4-4 || 1.2/50 µs shock waves immunity test IEC 61000-4-5 || conducted and radiated emissionsB CISPR 22 || conducted RF disturbances IEC 61000-4-6 || immunity to impulse waves IEC 61000-4-12
Net Weight
7 kg
Type Of Installation
indoor installation
Pollution Degree
2
Mounting Mode
socket-mounted
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
5-95 %
Mounting Support
enclosure door
Ip Degree Of Protection
front face IP65 || back IP51
Width
178 mm
Overvoltage Category
III
Depth
237 mm
Operating Altitude
0...9842.52 ft (0...3000 m)

Documents

Data Sheet

Download