Schneider Electric

SXWRCF16B10001

Description

SpaceLogic RP-C Pro Controller is a high performance multi-room , BACnet IP field controller for Connected Room solutions applications. The RP-C Pro controller has greater memory space and faster processing capabliities for large room and luxury suite applications. It can be used as a standalone BACnet/IP controller or as part of an EcoStruxure BMS with a AS-P, AS-B or an Enterprise Server as the parent server. The RP-C Pro features a wireless chip that allows the mobile commissioning application to connect directly to the controller. The RP-C-16B-24V has 8 universal I/O Type Ub, 4 solid-state relay outputs, 3 Form A relays and 1 high power relay outputs. Its dimensions are 164 mm (6.5 in.) in height, 181 mm (7.1 in.) in width and 64 mm (2.5 in.) in depth. Allows connection of up to 9 CRS extension modules per controller. It is a UL 916 (Open Class Energy Management Equipment) listed product for the United States and Canada - UL file E80146. The device can be mounted in a DIN rail or other flat surface inside a cabinet. Available optional covers (SXWRPCCOV10001), DIN-RAIL clip/end clip (SXWDINEND10001), eCommission Bluetooth Adapter (SXWBTAECXX10001).
Country of Origin
SE
Part Number
SXWRCF16B10001
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1902002EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1902002EN
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Specifications

Product Certifications
RCM || cUL Listed || UL Listed
Network Frequency
50 Hz || 60 Hz
[Us] Rated Supply Voltage
24 V AC +/- 15 % || 24...30 V DC || 23...33 V DC
Communication Port Support
ETHERNET 10/100BASE-TX
Number Of Outputs
3 form A relay output || 1 relay output || 4 solid-state relay output
Protection Type
internal fuse || built-in by varistor
Product Or Component Type
Field Controller
Input/Output Type
8 universal I/O
Range
SpaceLogic
Depth
64 mm
Height
110 mm
Function Available
Programmable || Smart Sensor Input
Memory Type
128 MB internal || 64 MB flash || 128 kB FRAM
Mounting Mode
DIN Rail Mount || panel-mounted
Color
Black
Ambient Air Temperature For Storage
-20-70 °C
Power Consumption In Va
30 VA
Relative Humidity
0-95 % RH, non-condensing
Product Weight
0.39 kg
Input Voltage
-0.5...24 V DC for universal input
Width
180 mm
Clock Drift
+/- 1 min/month
Device Application
HVAC || low voltage fan coil || chilled beam
Device Short Name
RP-C-16B-F-24V
Ip Degree Of Protection
IP20
Number Of Port
2 RJ45 || 1 USB type A female || 1 USB device port Mini-B

Complementary

Standards
EN 61000-6-3 || EN 50491-5-2 || FCC part 15 Subpart A class B || FCC part 15 Subpart C class B || UL 2043 || EN 61000-6-2 || EN 50491-5-3 || EN 60730-1 || EN 60730-2-11 || EN 50491-3 || UL 916 || ETSI EN 300 328 || ETSI EN 300 328:v2.1.1
Communication Port Protocol
BACnet IP || Bluetooth 5.0 LE 2.4 GHz || BACnet MS/TP
Backup Time
7 days
Product Name
RP-C Pro
Flame Retardance
UL94-5VB
Processor Name
ARM Cortex-A7
Analogue Input Type
configurable voltage, current or probe 0...2 mA || configurable voltage, current or probe 0...10 V input voltage || configurable voltage, current or probe 20 kOhm connection of probes || configurable voltage, current or probe 10 kOhm connection of probes || configurable voltage, current or probe 2.2 kOhm connection of probes || configurable voltage, current or probe 1.8 kOhm connection of probes || configurable voltage, current or probe 1 kOhm connection of probes

Documents

Data Sheet

Download