Schneider Electric TM3TM3G

analog IO module, Modicon TM3, 2 analog or temperature inputs, 1 analog output, spring, 24V DC

Image of the product TM3TM3G
This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The analogue I/O module provides 2 inputs, 1 output with 16bit, 15bit + sign input resolution. It is an I/O module with a rated supply voltage of 24V DC, a current consumption of 60mA, 55mA at 5V DC via bus connector, 55mA, 80mA at 24V DC via external supply. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an insulation between input and supply at 1500V AC, input and internal logic at 500V AC, output and supply at 1500V AC and output and internal logic at 500V AC. It is furnished with removable spring terminal for electrical connection with 5.08mm pitch adjustment for inputs, outputs and supply. It is an IP20 rated product. Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.1kg. This product is certified by CE. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

Additional information

Part Number TM3TM3G
EAN 3606480649059
UNSPSC 32151705
Tariff Code 85389099
RoHS Status Yes
Country of origin JP
Lifecycle status 00

Offer Sustainability

Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1402009EN
Sustainable Offer Status Green Premium product
Pvc Free Yes
Toxic Heavy Metal Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1402009EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

Specifications

Range Of Product Modicon TM3
Analogue Output Type current 4...20 mA || current 0...20 mA || voltage 0...10 V || voltage - 10...10 V
Product Or Component Type input/output analog module
Analogue Input Number 2
Analogue Output Number 1
Range Compatibility Modicon M221 || Modicon M241 || Modicon M251 || Modicon M262
Analogue Input Type current 4...20 mA || current 0...20 mA || voltage 0...10 V || voltage - 10...10 V || thermocouple - 200...1000 °C thermocouple J || thermocouple - 200...1300 °C thermocouple K || thermocouple 0...1760 °C thermocouple R || thermocouple 0...1760 °C thermocouple S || thermocouple 0...1820 °C thermocouple B || thermocouple - 200...400 °C thermocouple T || thermocouple - 200...1300 °C thermocouple N || thermocouple - 200...800 °C thermocouple E || thermocouple 0...2315 °C thermocouple C || Ni 100/Ni 1000 temperature probe - 60...180 °C || Pt 100 temperature probe - 200...850 °C || Pt 1000 temperature probe - 200...600 °C

Environment

Product Certifications CE || UKCA || RCM || EAC || cULus || cULus HazLoc
Resistance To Conducted Disturbances 10 V 0.15...80 MHz IEC 61000-4-6 || 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
Resistance To Electromagnetic Fields 10 V/m 80 MHz...1 GHz IEC 61000-4-3 || 3 V/m 1.4 GHz...2 GHz IEC 61000-4-3 || 1 V/m 2 GHz...3 GHz IEC 61000-4-3
Standards IEC 61131-2
Immunity To Microbreaks 10 ms
Ambient Air Temperature For Operation -10-55 °C horizontal installation || -10-35 °C vertical installation
Storage Altitude 0-3000 m
Pollution Degree 2
Shock Resistance 15 gn 11 ms
Resistance To Magnetic Fields 30 A/m IEC 61000-4-8
Vibration Resistance 3.5 mm 5-8.4 Hz DIN rail || 3 gn 8.4-150 Hz DIN rail
Ambient Air Temperature For Storage -25-70 °C
Relative Humidity 10-95 %, without condensation in operation) || 10-95 %, without condensation in storage)
Resistance To Electrostatic Discharge 8 kV in air IEC 61000-4-2 || 4 kV on contact IEC 61000-4-2
Ip Degree Of Protection IP20
Resistance To Fast Transients 1 kV IEC 61000-4-4 I/O)
Operating Altitude 0...6561.68 ft (0...2000 m)
Electromagnetic Emission radiated emissions 40 dBμV/m QP class A 10 m)30-230 MHz IEC 55011 || radiated emissions 47 dBμV/m QP class A 10 m)230-1000 MHz IEC 55011

Complementary

Electrical Connection 11 x 2.5 mm² removable spring terminal block pitch 5.08 mm for inputs, outputs and supply
Height 90 mm
Input Impedance <= 50 Ohm current || >= 1 MOhm voltage || >= 1 MOhm thermocouple || >= 1 MOhm temperature probe
Load Type resistive
Type Of Cable twisted shielded pairs cable <30 m input/output
Non-Linearity +/- 0.01 %FS analog output || +/- 0.1 %FS analog input
Lsb Value 0.15 mV 0...10 V voltage || 0.30 mV - 10...10 V voltage || 0.30 µA 0...20 mA current || 0.244 µA 4...20 mA current || 0.1 °C temperature probe || 0.1 °C thermocouple || 2.44 mV 0...10 V voltage || 4.88 mV - 10...10 V voltage || 4.88 µA 0...20 mA current || 3.91 µA 4...20 mA current
Permissible Continuous Overload 13 V voltage || 40 mA current
Marking CE
Analogue Input Resolution 16 bits || 15 bits + sign
Net Weight 0.1 kg
Absolute Accuracy Error +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C || +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C || +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C || +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C || +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C || +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C || +/- 0.1 % of full scale at 25 °C for analogue input voltage/current || +/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C || +/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe || +/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C || +/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C || +/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C || +/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C || +/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C || +/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C || +/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C || +/- 0.1 % of full scale at 25 °C for analogue output voltage/current
Current Consumption 55 mA 24 V DC via external supply no load || 55 mA 5 V DC via bus connector no load || 60 mA 5 V DC via bus connector full load || 80 mA 24 V DC via external supply full load
Conversion Time 100 ms + 100 ms per channel + 1 controller cycle time thermocouple || 100 ms + 100 ms per channel + 1 controller cycle time temperature probe || 10 ms + 10 ms per channel + 1 controller cycle time voltage/current
Analogue Output Resolution 12 bits
Temperature Drift +/- 0.006 %FS/°C
Supply Voltage Limits 20.4-28.8 V
Stabilisation Time 1 ms
Load Impedance Ohmic 1 kOhm voltage || 300 Ohm current
Output Ripple 20 mV
Mounting Support top hat type TH35-15 rail IEC 60715 || top hat type TH35-7.5 rail IEC 60715 || plate or panel with fixing kit
Local Signalling for PWR 1 LED (green)
Surge Withstand 1 kV power supply common mode IEC 61000-4-5 || 0.5 kV power supply differential mode IEC 61000-4-5 || 1 kV I/O common mode IEC 61000-4-5 || 0.5 kV I/O differential mode IEC 61000-4-5
Cross Talk <= 1 LSB
Width 23.6 mm
Depth 70 mm
[Us] Rated Supply Voltage 24 V DC
Insulation between input and supply 1500 V AC || between input and internal logic 500 V AC || between output and supply 1500 V AC || between output and internal logic 500 V AC
Sampling Duration 10 ms voltage/current || 100 ms voltage/current || 100 ms thermocouple || 100 ms temperature probe
Repeat Accuracy +/-0.5 %FS input || +/- 0.4 %FS output

CAD Models

TraceParts logo

TraceParts