¿Necesita más información?
ABB 2CDS282001R0404
S202P-C40 Miniature Circuit Breaker - 2P - C - 40 A
Descripción del producto
The S202P-C40 Miniature Circuit Breaker features a dual tripping mechanism, comprising a delayed thermal mechanism for overload protection and an electromechanical mechanism for short circuit protection. This model supports rated currents up to 40 A and operates efficiently across various configurations, including 2-pole setups.
Compliant with IEC/EN 60898-1, IEC/EN 60947-2, UL1077, and CSA 22.2 No. 235, it is suitable for residential, commercial, and industrial environments. The circuit breaker has an interruption capacity of up to 15 kA at 230 V AC and 400 V AC, ensuring reliable performance under short circuit conditions.
It is designed for easy installation on DIN rail TH35-15 and can accommodate a variety of connection types, including busbars and flexible conductors. The S202P-C40 also features a compact design, with a width of 35 mm and a height of 88 mm, allowing for efficient use of space. An auxiliary contact can be added to this model to enhance functionality while saving installation space.
Operating within a temperature range of -25 °C to +55 °C and with a degree of protection rated IP20, this miniature circuit breaker is built to withstand challenging environmental conditions. The device is designed for a mechanical endurance of up to 20,000 cycles and 10,000 AC cycles, ensuring long-term reliability in various applications.
¿Necesita más información?
Detalles de la oferta
- Oferta de:
- Proveedor de confianza — Polonia, miembro desde 2021, 50–99 empleados
- Disponibilidad:
- Bajo pedidoPlazo de entrega por confirmar
- Garantía:
- 12 meses
- Condición:
- Nuevo Precintado de Fábrica
Especificaciones
- Marca
- ABB
- Instructions and Manuals
- 2CDS207104P0002
- Standards
- CSA 22.2 No. 235IEC/EN 60898-1IEC/EN 60947-2UL 1077
- Tripping Characteristic
- C
- Rated Operational Voltage
- acc. to IEC 60898-1 400 V ACacc. to IEC 60947-2 400 V AC
- Operational Voltage
- Maximum (Incl. Tolerance) 125 V DCMaximum (Incl. Tolerance) 440 V ACMinimum 12 V ACMinimum 12 V DC
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 440 V
Ofertas disponibles
(3)| Condición | Disponibilidad | Proveedor | Garantía | Acción | |
|---|---|---|---|---|---|
| Condición Nuevo Precintado de Fábrica | Disponibilidad Bajo pedidoPlazo de entrega por confirmar | Proveedor PoloniaProveedor de confianza — miembro desde 2021, 50–99 empleados | Garantía 12 meses | ||
| Condición Nuevo Precintado de Fábrica | Disponibilidad Bajo pedidoPlazo de entrega por confirmar | Proveedor LetoniaProveedor de confianza — miembro desde 2024, 20–49 empleados | Garantía 12 meses | ||
| Condición Nuevo Precintado de Fábrica | Disponibilidad Bajo pedidoPlazo de entrega: 14–42 días | Proveedor FinlandiaProveedor de confianza — miembro desde 2026, 10–19 empleados | Garantía No indicada |
Oferta con plazo de entrega del fabricante
Directamente del fabricante, con un plazo de entrega confirmado, predecible y totalmente transparente.
Documentos
Hoja de datos
Hoja de datos para ABB 2CDS282001R0404, incluyendo especificaciones y características.
Modelos CAD
Modelo CAD 3D y planos técnicos, listos para tu software de diseño.
Datos del producto actualizados: 12-10-2026

Información de mercado de 2CDS282001R0404
Obtenga análisis en tiempo real y datos de mercado de 2CDS282001R0404 y productos similares para optimizar sus decisiones de compra.
- Datos de disponibilidad de existencias en tiempo real de más de 700 distribuidores MRO de Europa y EE.UU.
- Análisis de precios por estado (nuevos, usados, reacondicionados) con precios medios de mercado
- Supervisión de la disponibilidad de componentes críticos para evitar paradas de producción