Schneider Electric
ATV630U15N4
1 / 5
Descripción
Activo maduro
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 480V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 1.5kW / 2hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 0.75kW / 1hp for applications requiring significant overload (up to 150%). It weighs 4.5kg and its dimensions are, 144mm wide, 350mm high, 203mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.- Country of Origin
- ID
- Part Number
- ATV630U15N4
- Tariff Code
- 85044095
- EAN
- 3606480758102
- UNSPSC
- 39122001
€477.84
net€543.00
Envío gratis!1
Métodos de pago:
- Mejor oferta de:
- Proveedor de confianza de Automa.Net
- Disponibilidad:
- 1 piezaEn stockActualizado en: 09-11-2024
- Garantía:
- 24 meses
- Entrega Estimada:
- 12 noviembre a Reino Unido
- Condición:
- Nuevo Precintado de Fábrica
Nuevo Precintado de Fábrica - Un artículo completamente nuevo, sin usar, sin abrir, sin daños, en su embalaje original sellado por el fabricante.
Información de envío
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía
Offer Sustainability
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Upgradeability
- Upgraded components available
- Rohs Exemption Information
- Yes
- Environmental Disclosure
- ENVPEP1501005EN
- Sustainable Offer Status
- Green Premium product
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Circularity Profile
- ENVEOLI1501005EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Discrete Input Logic
- positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
- Analogue Output Type
- software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
- Discrete Output Type
- relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V DC 5000 mA
- Maximum Switching Current
- relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
- Exchange Mode
- half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
- Power Range
- 1.1-2 kW 380-440 V 3 phase || 1.1-2 kW 480-500 V 3 phase
- Phase
- 3 phase
- Net Weight
- 4.5 kg
- Type Of Polarization
- no impedance
- Frequency Resolution
- display unit 0.1 Hz || analog input 0.012/50 Hz
- Relay Output Type
- configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
- Maximum Transient Current
- 4.4 A 60 s normal duty) || 3.3 A 60 s heavy duty)
- Analogue Input Number
- 3
- Motor Slip Compensation
- can be suppressed || adjustable || not available in permanent magnet motor law || automatic whatever the load
- Discrete Output Number
- 0
- Method Of Access
- slave Modbus TCP
- Discrete Input Number
- 8
- Local Signalling
- for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
- Linearity Error
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
- Number Of Addresses
- 1-247 Modbus serial
- Width
- 144 mm
- Transmission Rate
- 10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
- Depth
- 203 mm
- Analogue Input Type
- AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
- Discrete And Process Manufacturing
- building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compressor || food and beverage processing pump || food and beverage processing fan || food and beverage processing atomization || oil and gas electro submersible pump (ESP) || oil and gas water injection pump || oil and gas jet fuel pump || oil and gas compressor for refinery || water and waste water centrifuge pump || water and waste water positive displacement pump || water and waste water electro submersible pump (ESP) || water and waste water screw pump || water and waste water lobe compressor || water and waste water screw compressor || water and waste water compressor centrifugal || water and waste water fan || water and waste water conveyor || water and waste water mixer
- Sampling Duration
- 2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
- Electrical Connection
- control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 2.5...6 mm² AWG 14...AWG 10 || line side screw terminal 2.5...6 mm² AWG 14...AWG 10
- Maximum Output Frequency
- 500 kHz
- Height
- 350 mm
- Acceleration And Deceleration Ramps
- linear adjustable separately from 0.01...9999 s
- Transmission Frame
- RTU
- Relay Output Number
- 3
- Data Format
- 8 bits, configurable odd, even or no parity
- Accuracy
- +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
- Connector Type
- RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
- Input Compatibility
- DI1...DI6 discrete input level 1 PLC EN/IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC EN/IEC 61131-2
- Permissible Temporary Current Boost
- 1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
- Mounting Mode
- wall mount
- Analogue Output Number
- 2
- Physical Interface
- Ethernet || 2-wire RS 485
- Minimum Switching Current
- relay output R1, R2, R3 5 mA 24 V DC
- Refresh Time
- relay output R1, R2, R3)5 ms +/- 0.5 ms)
- Enclosure Mounting
- wall mounted
- Isolation
- between power and control terminals
- Output Voltage
- <= power supply voltage
- Quantity Per Set
- 1
- Braking To Standstill
- by DC injection
- Discrete Input Type
- DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
- Protection Type
- thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || motor phase break drive || overvoltages on the DC bus drive || line supply overvoltage drive || line supply undervoltage drive || line supply phase loss drive || overspeed drive || break on the control circuit drive
- Supply
- external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
Specifications
- Prospective Line Isc
- 50 kA
- Product Destination
- asynchronous motors || synchronous motors
- Line Current
- 3 A 380 V normal duty) || 2.6 A 480 V normal duty) || 1.7 A 380 V heavy duty) || 1.5 A 480 V heavy duty)
- Emc Filter
- integrated 50 m EN/IEC 61800-3 category C2 || integrated 150 m EN/IEC 61800-3 category C3
- Asynchronous Motor Control Profile
- variable torque standard || constant torque standard || optimized torque mode
- Variant
- standard version
- Product Or Component Type
- variable speed drive
- Apparent Power
- 2.2 kVA 480 V normal duty) || 1.2 kVA 480 V heavy duty)
- Switching Frequency
- 2...12 kHz adjustable || 4...12 kHz with derating factor
- Communication Port Protocol
- Modbus TCP || Ethernet || Modbus serial
- Product Specific Application
- process and utilities
- Safety Function
- STO (safe torque off) SIL 3
- Maximum Horse Power Rating
- 2 hp normal duty || 1 hp heavy duty
- Supply Frequency
- 50...60 Hz - 5...5 %
- Option Card
- slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A communication module, CANopen SUB-D 9 || slot A communication module, CANopen screw terminals || slot A/slot B digital and analog I/O extension module || slot A/slot B output relay extension module || slot A communication module, Ethernet IP/Modbus TCP/MD-Link || communication module, BACnet MS/TP || communication module, Ethernet Powerlink
- Degree Of Protection
- UL type 1 UL 508C
- Range Of Product
- Altivar Process ATV600
- Speed Drive Output Frequency
- 0.1-500 Hz
- Ip Degree Of Protection
- IP21IEC 61800-5-1 || IP21IEC 60529
- Motor Power Kw
- 1.5 kW normal duty) || 0.75 kW heavy duty)
- [Us] Rated Supply Voltage
- 380...480 V
- [Us] Rated Supply Voltage
- 380...480 V - 15...10 %
- Discrete Input Logic
- 16 preset speeds
- Type Of Cooling
- forced convection
- Continuous Output Current
- 4 A 4 kHz normal duty || 2.2 A 4 kHz heavy duty
- Nominal Switching Frequency
- 4 kHz
- Device Short Name
- ATV630
- Synchronous Motor Control Profile
- permanent magnet motor || synchronous reluctance motor
Environment
- Product Certifications
- ATEX INERIS || DNV-GL || ATEX zone 2/22 || UL || CSA || TÜV
- Power Dissipation In W
- natural convection 28 W 380 V 4 kHz || forced convection 41 W 380 V 4 kHz
- Standards
- UL 508C || EN/IEC 61800-3 || EN/IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || EN/IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
- Insulation Resistance
- > 1 MOhm 500 V DC for 1 minute to earth
- Shock Resistance
- 15 gn 11 ms IEC 60068-2-27
- Vibration Resistance
- 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
- Noise Level
- 54.5 dB 86/188/EEC
- Regulation Loop
- adjustable PID regulator
- Operating Altitude
- <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
- Overvoltage Category
- III
- Pollution Degree
- 2
- Electromagnetic Compatibility
- electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6
- Ambient Air Temperature For Operation
- -15-50 °C without derating) || 50-60 °C with derating factor)
- Volume Of Cooling Air
- 38 m3/h
- Marking
- CE
- Pollution Degree
- 2 EN/IEC 61800-5-1
- Noise Level
- 54.5 dB
- Ambient Air Temperature For Storage
- -40-70 °C
- Relative Humidity
- 5-95 % without condensation IEC 60068-2-3
- Operating Position
- vertical +/- 10 degree
- Maximum Thdi
- <48 % full load IEC 61000-3-12
Modelos CAD