Schneider Electric
BCPME242S
1 / 1
Descripción
Activo maduro
This is an integrated solution for monitoring multi-circuits and mains by using a single meter. The meter is designed for use in new build and is used for critical power operations in data centres and energy management in buildings. It offers class 1 (1 %) power and energy system accuracy (100A solid core current transformers) on all branch channels. The BCPM monitors both the 42 branch circuits and mains values, incoming power and energy. All to provide information on the complete Power Distribution Unit. Full alarming capabilities ensure that potential issues are dealt with before they become problems. Communication enabled with serial connection for either Modbus RTU or BACnet MS/TP, and an Ethernet connection for Modbus TCP, BACnet IP and SNMP. The meter need to be powered by a 100V AC to 277V AC supply source. Include 2 21-CTs board strips with 18mm spacing between each CT connectors, for 42 circuits. The device dimensions are 353mm in width, 253mm in height, 71mm in depth and weight 1.5 kilograms.- Part Number
- BCPME242S
- Tariff Code
- 9028300000
- EAN
- 83101808
- UNSPSC
- 83101808
- Consigue plazos de pago de hasta 90 días de 500+ proveedores.
- Descuentos de reventa de hasta el 40%!
Enviar solicitud de precio
1
Formas de pago:
Complementary
- Communication Port Support
- RS485 || ETHERNET
- Connection Pitch
- 18 mm
- Measurement Voltage
- 90-277 V phase to neutral || 150-480 V phase to phase
- Sampling Rate
- 256 samples/cycle
- Communication Port Protocol
- Modbus RTU || BACnet IP || BACnet MS/TP || Modbus TCP || SNMP v2
- Communication Of Data
- high-high current alarm || under voltage alarm || over voltage alarm || low-low current alarm || high current alarm || low current alarm
- Provided Equipment
- 42 x current transformer || 2 x cables
- Measurement Accuracy
- branch current 2 % 0.25…2 A || branch current 1 % 2…100 A || mains current 3 % 1…100 % || mains current 3 % 2…100 % || voltage 1 % 90…277 V
- Update Time
- 1.8 s
- Analogue Input Type
- solid core CT 100 A42 x
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Eu Rohs Directive
- Compliant with Exemptions
Environment
- Height
- 307 mm
- Standards
- IEC 61036 || UL 508 || ANSI C12.1 || EN 61010
- Mounting Support
- panel || enclosure
- Product Certifications
- UL
- Net Weight
- 1.5 kg
- Mounting Mode
- panel-mounted
- Ambient Air Temperature For Storage
- -40-70 °C
- Relative Humidity
- 0-95 % 0-60 °C
- Width
- 253 mm
- Depth
- 71 mm
- Operating Altitude
- 9842.52 ft (3000 m)
Specifications
- Network Frequency
- 50 Hz || 60 Hz
- Power Quality Analysis
- voltage sag and swell detection
- Variant
- advanced + ethernet
- Type Of Measurement
- voltage || current || frequency || active power || power factor || active energy
- Power Monitoring
- basic instrumentation
- Product Or Component Type
- multi-circuit energy meter
- Product Name
- PowerLogic BCPM
- Range
- PowerLogic
- Energy Management
- sub billing and cost allocation
- [Us] Rated Supply Voltage
- 90...277 V AC 50/60 Hz +/- 1 %
- Device Application
- sub billing
- Device Short Name
- BCPME
Documentos
Data Sheet
DescargarOtras categorías
ActuadoresBloquesCables, tuberías y manguerasCompresoresControlAcoplamientos y AccesoriosCilindros y PistonesElectrónicaFiltrosHVACPCs industriales y HMIsIluminaciónTécnica linealMotoresFuente de alimentaciónTransmisión de energíaBombas y VálvulasEnergías renovablesRobóticaSellos, anillos y conectoresSensores y dispositivos de mediciónHerramientas y AccesoriosCNCOtros