TeSys GV electrical trip unit, MX shunt trip, 380-415V AC 50Hz / 440-480V AC 60Hz, for motor circuit breakers GV4. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be plugged inside the circuit breaker, connection by spring terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).- Country of Origin
- FR
- Part Number
- GV4AS487
- Tariff Code
- 85363010
- EAN
- 3606485444925
- UNSPSC
- 39121010
- Consigue plazos de pago de hasta 90 días de 500+ proveedores.
- Descuentos de reventa de hasta el 40%!
Enviar solicitud de precio
1
Formas de pago:
Specifications
- [Uc] Control Circuit Voltage
- 440...480 V AC 60 Hz || 380...415 V AC 50 Hz
- Range Compatibility
- TeSys TeSys GV4 || TeSys TeSys BV4
- Product Or Component Type
- voltage release
- Range
- TeSys
- Voltage Release Type
- shunt trip release
- Device Application
- control
- Device Short Name
- MX
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2311043EN
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2311043EN
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- Maximum Inrush Power In Va
- 6 VA
- Connections - Terminals
- spring terminals 1 0.5-1.5 mm² - cable stiffness: flexible without cable end
- Wire Stripping Length
- 8 mm
- [Ui] Rated Insulation Voltage
- 480 V IEC 60947-1
- Impulse Duration
- >= 20 ms
- Mounting Mode
- internal mounting
- Mechanical Durability
- 20000 cycles
- Maximum Hold-In Power Consumption In Va
- 10 VA
- Threshold Tripping Voltage
- 0.7...1.1 Un failsafe opening || < 0.7 Un possible opening
- Operating Time
- < 50 ms