1 / 1
thumbnail

Descripción

Activo maduro
TeSys GV electrical trip unit, MN undervoltage release, 110-130V AC 50/60Hz and 125V DC, for motor circuit breakers GV4. Opening of the the circuit breaker is ensured when the control voltage drops below 0.35 Uc, and possible between 0.35-0.7 Uc. Closing of the circuit breaker is possible when the control voltage is in limits 0.85-1.1 Uc. To be plugged inside the circuit breaker, connection by spring terminals. Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).
Country of Origin
FR
Part Number
GV4AU137
Tariff Code
85363010
EAN
3606485444833
UNSPSC
39121010
Métodos de pago:
Mejor oferta de:
PLProveedor de confianza de Automa.Net
Disponibilidad:
1 pieza
En stock
Actualizado en: 17-09-2024
Garantía:
12 meses
Entrega Estimada:
Bajo pedido
Condición:
Nuevo Precintado de Fábrica
Nuevo Precintado de Fábrica - Un artículo completamente nuevo, sin usar, sin abrir, sin daños, en su embalaje original sellado por el fabricante.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2311042EN
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2311042EN
Eu Rohs Directive
Compliant with Exemptions

Specifications

[Uc] Control Circuit Voltage
110...130 V AC 50/60 Hz || 125 V DC
Range Compatibility
TeSys TeSys GV4 || TeSys TeSys BV4
Product Or Component Type
voltage release
Range
TeSys
Voltage Release Type
undervoltage release
Device Application
control
Device Short Name
MN

Complementary

Maximum Inrush Power In W
2 W
Maximum Inrush Power In Va
7 VA
Connections - Terminals
spring terminals 1 0.5-1.5 mm² - cable stiffness: flexible without cable end
Wire Stripping Length
8 mm
[Ui] Rated Insulation Voltage
130 V IEC 60947-1
Mounting Mode
internal mounting
Maximum Hold-In Power Consumption In W
2 W
Mechanical Durability
20000 cycles
Maximum Hold-In Power Consumption In Va
7 VA
Threshold Tripping Voltage
< 0.35 Un failsafe opening || 0.35...0.7 Un possible opening || 0.85...1.1 Un enabled closing
Operating Time
< 50 ms

Environment

Quantity Per Set
set of 1

Modelos CAD