Undervoltage release, TeSys GV4, MN coil, 110 to 130VAC 50/60Hz, 125VDC
GV4AU137
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
€52.01
1
Formas de pago:

Additional Information

Part Number
GV4AU137
UNSPSC
39121010
Tariff Code
8536308000

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2311042EN
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2311042EN
Eu Rohs Directive
Compliant with Exemptions

Specifications

[Uc] Control Circuit Voltage
110...130 V AC 50/60 Hz || 125 V DC
Range Compatibility
TeSys TeSys GV4 || TeSys TeSys BV4
Product Or Component Type
voltage release
Range
TeSys
Voltage Release Type
undervoltage release
Device Application
control
Device Short Name
MN

Complementary

Maximum Inrush Power In W
2 W
Maximum Inrush Power In Va
7 VA
Connections - Terminals
spring terminals 1 0.5-1.5 mm² - cable stiffness: flexible without cable end
Wire Stripping Length
8 mm
[Ui] Rated Insulation Voltage
130 V IEC 60947-1
Mounting Mode
internal mounting
Maximum Hold-In Power Consumption In W
2 W
Mechanical Durability
20000 cycles
Maximum Hold-In Power Consumption In Va
7 VA
Threshold Tripping Voltage
< 0.35 Un failsafe opening || 0.35...0.7 Un possible opening || 0.85...1.1 Un enabled closing
Operating Time
< 50 ms

Environment

Quantity Per Set
set of 1

Documentos

Data Sheet

Descargar

Modelos CAD

Rastrear piezas
Rastrear piezas
Descargar