IEC contactor, TeSys Deca, nonreversing, 115A, 75HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 48VAC 50/60Hz coil, open
LC1D115E7
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Un total de 38 Parts In-Stock de 23 Distributors

Additional Information

Part Number
LC1D115E7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Product Certifications
DNV || CCC || RINA || GOST || BV || GL || LROS (Lloyds register of shipping) || CSA || UL || UKCA || CE
Height
158 mm
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Climatic Withstand
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight
2.5 kg
Flame Retardance
V1 conforming to UL 94
Protective Treatment
THIEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
120 mm
Depth
136 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C || 60-70 °C with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP060301EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI100405
Eu Rohs Directive
Compliant with Exemptions

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Power Dissipation Per Pole
24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
Average Impedance
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
200 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
0.3...0.5 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55 °C operational AC 50/60 Hz || 1...1.15 Uc 55-70 °C operational AC 50/60 Hz
Mounting Support
plate || rail
Contact Compatibility
M13
Control Circuit Type
AC 50/60 Hz standard
Safety Reliability Level
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree
3
Insulation Resistance
> 10 MOhm for signalling circuit
Rated Breaking Capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
Associated Fuse Rating
250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for signalling circuit
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947
Inrush Power In Va
280-350 VA 60 Hz cos phi 0.8 (at 20 °C) || 280-350 VA 50 Hz cos phi 0.8 (at 20 °C)
Pole Contact Composition
3 NO
Connections - Terminals
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: solid without cable end || power circuit: connector 1 10-120 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 10-50 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 10-120 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 10-50 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 10-120 mm² - cable stiffness: solid without cable end || power circuit: connector 2 10-50 mm² - cable stiffness: solid without cable end
Coil Technology
built-in bidirectional peak limiting diode suppressor
Operating Time
6...20 ms opening || 20...50 ms closing
Minimum Switching Voltage
17 V for signalling circuit
Maximum Operating Rate
2400 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Mechanical Durability
8 Mcycles
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code
LC1D
Hold-In Power Consumption In Va
2-18 VA 60 Hz cos phi 0.3 (at 20 °C) || 2-18 VA 50 Hz cos phi 0.3 (at 20 °C)
Overvoltage Category
III
Maximum Horse Power Rating
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Motor Power Kw
30 kW at 220...230 V AC 50/60 Hz (AC-3) || 55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415...440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 65 kW at 1000 V AC 50/60 Hz (AC-3) || 18.5 kW at 400 V AC 50/60 Hz (AC-4) || 30 kW at 220...230 V AC 50/60 Hz (AC-3e) || 55 kW at 380...400 V AC 50/60 Hz (AC-3e) || 59 kW at 415...440 V AC 50/60 Hz (AC-3e) || 75 kW at 500 V AC 50/60 Hz (AC-3e) || 80 kW at 660...690 V AC 50/60 Hz (AC-3e) || 65 kW at 1000 V AC 50/60 Hz (AC-3e)
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
[Icw] Rated Short-Time Withstand Current
250 A 40 °C - 10 min for power circuit || 550 A 40 °C - 1 min for power circuit || 950 A 40 °C - 10 s for power circuit || 1100 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Heat Dissipation
3-8 W at 50/60 Hz
Protective Cover
with

Specifications

[Uc] Control Circuit Voltage
48 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of Product
TeSys Deca
Contactor Application
motor control || resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1 || AC-4 || AC-3 || AC-3e
[Ie] Rated Operational Current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 115 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Poles Description
3P
Device Short Name
LC1D