TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 630 A - coil 220 V AC
LC1F630M7
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
$5,012.57
1
Formas de pago:
Un total de 7 Parts In-Stock de 12 Distributors
Oferta con plazo de entrega del fabricante
Entrega:1 - 2 días laborables
El mejor precio:
€1,542.85

Additional Information

Part Number
LC1F630M7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Specifications

[Uc] Control Circuit Voltage
220 V AC 40...400 Hz
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 1000 V AC 50/60 Hz || <= 460 V DC
Contactor Application
resistive load || motor control
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-3 || AC-1 || AC-4
[Ie] Rated Operational Current
1000 A 40 °C) <= 440 V AC AC-1 || 630 A 55 °C) <= 440 V AC AC-3
Poles Description
3P
Device Short Name
LC1F

Contractual warranty

Warranty
18 months

Complementary

Product Certifications
LROS (Lloyds register of shipping) || CB || UL || RMRoS || CSA || ABS || BV || DNV || RINA || UKCA
Power Dissipation Per Pole
120 W AC-1 || 48 W AC-3
Average Impedance
0.12 mOhm - Ith 1000 A 50 Hz
[Ith] Conventional Free Air Thermal Current
1000 A 40 °C || 1250 A
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.25...0.5 Uc 40...400 Hz 55 °C)
Standards
EN 60947-1 || IEC 60947-4-1 || JIS C8201-4-1 || IEC 60947-1 || EN 60947-4-1
Mounting Support
plate
Control Circuit Type
AC 40...400 Hz
Contactor Coil Voltage
220 V AC standard
Rated Breaking Capacity
5040 A IEC 60947-4-1
Power Range
250-500 kW 380-440 V 3 phase || 110-220 kW 200-240 V 3 phase || 250-500 kW 480-500 V 3 phase
Associated Fuse Rating
1000 A gG <= 440 V || 630 A aM <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
1650-1650 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 60 x 5 mm || power circuit bolted connection
Pole Contact Composition
3 NO
Motor Starter Type
direct on-line contactor
Operating Time
40...80 ms closing || 100...200 ms opening
Maximum Operating Rate
1200 cyc/h 55 °C
Mechanical Durability
5 Mcycles
Tightening Torque
control circuit 1.2 N.m || power circuit 58 N.m
Compatibility Code
LC1F
Hold-In Power Consumption In Va
22-22 VA, 40...400 Hz 0.9 20 °C)
Overvoltage Category
III
Motor Power Kw
335 kW 380...400 V AC 50/60 Hz AC-3) || 375 kW 415 V AC 50/60 Hz AC-3) || 400 kW 440 V AC 50/60 Hz AC-3) || 400 kW 500 V AC 50/60 Hz AC-3) || 450 kW 660...690 V AC 50/60 Hz AC-3) || 450 kW 1000 V AC 50/60 Hz AC-3) || 200 kW 220...230 V AC 50/60 Hz AC-3) || 100 kW 400 V AC 50/60 Hz AC-4)
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
5050 A 40 °C - 10 s || 4400 A 40 °C - 30 s || 3400 A 40 °C - 1 min || 2200 A 40 °C - 3 min || 1600 A 40 °C - 10 min
Heat Dissipation
20-20 W

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1505009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1505009EN
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-5-55 °C
Height
304 mm
Net Weight
18.6 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Width
309 mm
Depth
255 mm
Permissible Ambient Air Temperature Around The Device
-40-70 °C

Modelos CAD

Rastrear piezas
Rastrear piezas
Descargar