Contactor, TeSys K, 4P, 4 NO, AC-1, lt or eq to 440V 10A, 230VAC coil
LC1K12004P7
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
€22.73
1
Formas de pago:
Un total de 177 Parts In-Stock de 19 Distributors
Oferta con plazo de entrega del fabricante
Entrega:1 - 2 días laborables
El mejor precio:
€14.32

Additional Information

Part Number
LC1K12004P7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
FR

Environment

Product Certifications
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Standards
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Flame Retardance
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Protective Treatment
TC IEC 60068 || TC DIN 50016
Operating Altitude
6561.68 ft (2000 m) without derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503003EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1503003EN
Eu Rohs Directive
Compliant

Complementary

Mechanical Robustness
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
[Uc] Control Circuit Voltage
230 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC <= 400 Hz || signalling circuit <= 690 V AC <= 400 Hz
Height
58 mm
Average Impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
Control Circuit Voltage Limits
operational: 0.8...1.15 Uc (at <50 °C) || drop-out: >= 0.20 Uc (at <50 °C)
[Ith] Conventional Free Air Thermal Current
20 A (at 60 °C) for power circuit || 10 A (at 50 °C) for signalling circuit
Control Circuit Type
AC 50/60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Rated Breaking Capacity
110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
Irms Rated Making Capacity
144 A AC for power circuit conforming to IEC 60947
Associated Fuse Rating
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
30-30 VA (at 20 °C)
Connections - Terminals
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end
Pole Contact Composition
4 NO
Utilisation Category
AC-1
[Ie] Rated Operational Current
20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Maximum Operating Rate
3600 cyc/h
Signalling Circuit Frequency
<= 400 Hz
Electrical Durability
0.3 Mcycles 20 A AC-1 <= 690 V
Mechanical Durability
10 Mcycles
Poles Description
4P
Hold-In Power Consumption In Va
4.5-4.5 VA (at 20 °C)
Operating Time
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Width
45 mm
Overvoltage Category
III
Depth
57 mm
[Icw] Rated Short-Time Withstand Current
115 A 50 °C - 1 s for power circuit || 105 A 50 °C - 5 s for power circuit || 100 A 50 °C - 10 s for power circuit || 75 A 50 °C - 30 s for power circuit || 55 A 50 °C - 1 min for power circuit || 50 A 50 °C - 3 min for power circuit || 25 A 50 °C - >= 15 min for power circuit
Heat Dissipation
1.3-1.3 W

Specifications

Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Device Application
control

Documentos

Data Sheet

Descargar

Modelos CAD

Rastrear piezas
Rastrear piezas
Descargar

Productos relacionados