Standard control unit, TeSys Ultra, 1.25A to 5A, 3P motors, thermal magnetic protection, class 10, coil 48-72VAC/DC
LUCA05ES
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
£65.00
1
Formas de pago:
Un total de 2 Parts In-Stock de 14 Distributors

Environment

Ambient Air Temperature For Operation
-25-70 °C
Resistance To Radiated Fields
10 V/m 3 IEC 61000-4-3
Non-Dissipating Shock Wave
1 kV serial mode IEC 60947-6-2 || 2 kV common mode IEC 60947-6-2
Shock Resistance
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Vibration Resistance
2 gn 5-300 Hz power poles open IEC 60068-2-6 || 4 gn 5-300 Hz power poles closed IEC 60068-2-6
Immunity To Microbreaks
3 ms
Immunity To Voltage Dips
70 % / 500 ms IEC 61000-4-11
Ip Degree Of Protection
IP20 front panel and wired terminals IEC 60947-1 || IP20 other faces IEC 60947-1 || IP40 front panel outside connection zone IEC 60947-1
Ambient Air Temperature For Storage
-40-85 °C
Protective Treatment
TH IEC 60068
Resistance To Electrostatic Discharge
8 kV 3 in open air IEC 61000-4-2 || 8 kV 4 on contact IEC 61000-4-2
Operating Altitude
6561.68 ft (2000 m)
Fire Resistance
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Immunity To Radioelectric Fields
10 V IEC 61000-4-6
Resistance To Fast Transients
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP080204EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI100414
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Product Certifications
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Height
66 mm
Net Weight
0.135 kg
Fixing Mode
plug-in front face)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-6-2
Standards
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Typical Current Consumption
280 mA 48 V AC I maximum while closing with LUB12 || 280 mA 48 V AC I maximum while closing with LUB32 || 280 mA 48 V AC I maximum while closing with LUB38 || 280 mA 48...72 V DC I maximum while closing with LUB12 || 280 mA 48...72 V DC I maximum while closing with LUB32 || 280 mA 48...72 V DC I maximum while closing with LUB38 || 35 mA 48 V AC I rms sealed with LUB12 || 45 mA 48 V AC I rms sealed with LUB32 || 45 mA 48 V AC I rms sealed with LUB38 || 35 mA 48...72 V DC I rms sealed with LUB12 || 45 mA 48...72 V DC I rms sealed with LUB32 || 45 mA 48...72 V DC I rms sealed with LUB38
[Ui] Rated Insulation Voltage
690 V IEC 60947-6-2 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Compatibility Code
LUCA
Control Circuit Voltage Limits
38.5...72 V AC 48 V in operation || 38.5...93 V DC 48...72 V in operation || 29 V AC 48 V drop-out || 29 V DC 48...72 V drop-out
Operating Time
35 ms opening with LUB12 control circuit || 35 ms opening with LUB32 control circuit || 35 ms opening with LUB38 control circuit || 60 ms closing with LUB12 control circuit || 60 ms closing with LUB32 control circuit || 60 ms closing with LUB38 control circuit
Width
45 mm
Safe Separation Of Circuit
400 V SELV between the control and auxiliary circuits IEC 60947-1 || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Depth
60 mm
Heat Dissipation
2-2 W control circuit with LUB12 || 3-3 W control circuit with LUB32 || 3-3 W control circuit with LUB38

Specifications

[Uc] Control Circuit Voltage
48 V AC || 48...72 V DC
[Ue] Rated Operational Voltage
690 V AC
Range Of Product
TeSys Ultra
Phase Failure Sensitivity
yes
Thermal Protection Adjustment Range
1.25-5 A
Product Or Component Type
standard control unit
Product Name
TeSys Ultra
Thermal Overload Class
class 10 40-60 Hz -25-70 °C IEC 60947-6-2 || class 10 40-60 Hz -25-70 °C UL 508
Motor Power Kw
1.5 kW 400...440 V AC 50/60 Hz || 2.2 kW 500 V AC 50/60 Hz || 3 kW 690 V AC 50/60 Hz
Range
TeSys
Utilisation Category
AC-41 || AC-43 || AC-44
Function Available
earth fault protection || manual reset || protection against overload and short-circuit || protection against phase failure and phase imbalance
Tripping Threshold
14.2 x Ir +/- 20 %
Product Compatibility
power base LUB12 || power base LUB32 || power base LUB38 || power base LUB120 || power base LUB320 || power base LUB380 || reversing contactor breaker LU2B12ES || reversing contactor breaker LU2B32ES
Product Specific Application
basic protection requirements for motor starters: overload and short-circuit
Network Frequency
40...60 Hz
Load Type
3-phase motor self-cooled
Device Application
motor control || motor protection
Device Short Name
LUCA

Documentos

Data Sheet

Descargar

Modelos CAD

Rastrear piezas
Rastrear piezas
Descargar

Productos relacionados