Schneider Electric
LV848064
1 / 1
Descripción
This is a basic frame for 4 poles Masterpact MTZ2 20H1 fixed circuit breaker. Masterpact MTZ is the last generation of high current air circuit breakers up to 6300 A embedding advanced digital technologies. Masterpact MTZ is designed to protect electrical systems from damage caused by overloads, short circuits and equipment ground faults. The breaking capacity (Icu) is 66kA rms at 440VAC 50/60Hz. The rated current is 2000A. The basic frame must be associated with the corresponding chassis which has also to be ordered separately. This basic frame is compatible with Micrologic X control unit which has to be ordered separately. With Micrologic X control unit, Masterpact MTZ contributes to safety and energy efficiency. It can be equipped with a variety of optional functions and accessories. The dimensions are 537mm (W) x 352mm (H) x 300mm (D). It ensures compliance with international standards (IEC 60947), UL489, CCC, EAC and marine specifications. Masterpact MTZ and Micrologic X are part of EcoStruxure architecture system.- Country of Origin
- FR
- Part Number
- LV848064
- Tariff Code
- 85362090
- EAN
- 3606480808395
- UNSPSC
- 39121601
Métodos de pago:
- Mejor oferta de:
- Proveedor de confianza de Automa.Net
- Disponibilidad:
- 1 piezaEn stockActualizado en: 09-11-2024
- Garantía:
- 12 meses
- Entrega Estimada:
- Bajo pedido
- Condición:
- Nuevo Precintado de Fábrica
Nuevo Precintado de Fábrica - Un artículo completamente nuevo, sin usar, sin abrir, sin daños, en su embalaje original sellado por el fabricante.
Información de envío
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía
Specifications
- Network Frequency
- 50/60 Hz
- Network Type
- AC
- Breaking Capacity Code
- H1
- Product Or Component Type
- circuit breaker
- Product Name
- MasterPact MTZ2
- Range
- Masterpact
- Utilisation Category
- category B
- Suitability For Isolation
- yes IEC 60947-2
- Poles Description
- 4P
- Neutral Position
- left
- Device Application
- protection
- Device Short Name
- MTZ2 20 H1
Complementary
- [Ics] Rated Service Breaking Capacity
- 66 kA 220/415 V AC 50/60 Hz IEC 60947-2 || 66 kA 440 V AC 50/60 Hz IEC 60947-2 || 66 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 66 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Line Rated Current
- 2000 A 40 °C
- Connection Pitch
- 115 mm
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Mounting Support
- base plate || rails
- Circuit Breaker Ct Rating
- 2000 A
- Maximum Breaking Time
- 25-25 ms
- Depth
- 300 mm
- Control Type
- push-button
- Maximum Closing Response Time
- 70 ms
- Mounting Mode
- fixed
- Breaking Capacity
- 66 kA Icu 220/415 V AC 50/60 Hz IEC 60947-2 || 66 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 66 kA Icu 500/525 V AC 50/60 Hz IEC 60947-2 || 66 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- [Icm] Rated Short-Circuit Making Capacity
- 145 kA 220/415 V AC 50/60 Hz || 145 kA 440 V AC 50/60 Hz || 145 kA 500/525 V AC 50/60 Hz || 145 kA 660/690 V AC 50/60 Hz
- Electrical Durability
- AC-3 6000 cycles 440/690 V AC 50/60 Hz IEC 60947-3 || 6000 cycles 690 V AC 50/60 Hz IEC 60947-2 || 8000 cycles 440 V AC 50/60 Hz IEC 60947-2 || AC-23A 6000 cycles 690 V AC 50/60 Hz IEC 60947-3 || AC-23A 8000 cycles 440 V AC 50/60 Hz IEC 60947-3
- [Ui] Rated Insulation Voltage
- 1000 V AC 50/60 Hz IEC 60947-2
- Mechanical Durability
- 20000 cycles with periodic preventive maintenance IEC 60947-2
- Height
- 352 mm
- Width
- 537 mm
- [Uimp] Rated Impulse Withstand Voltage
- 12 kVIEC 60947-2
- [Icw] Rated Short-Time Withstand Current
- 66 kA 0.5 s IEC 60947-2 || 66 kA 1 s IEC 60947-2 || 36 kA 3 s IEC 60947-2
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1607009EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1607009EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- ASTA
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- IEC 60947-2 || IEC 60364-8-1
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -40-85 °C
Modelos CAD
traceparts
Descargar