Schneider Electric
LV850003
1 / 1
Descripción
This is the digital module "Waveform Capture on trip event" for Micrologic X trip unit on Masterpact MTZ offer. A digital module is an advanced function that can be uploaded in Micrologic X trip unit at any stage of the product life cycle. Digital modules allow you to customize MasterPact MTZ circuit breaker to your specific needs. The digital modules are available 24/7 on the Schneider Electric GoDigital store (godigital.schneider-electric.com). The upload of the digital modules is made without interrupting power, using EcoStruxure Power Commission software and a USB cable. This digital module automatically logs 5 cycles of phase and neutral currents, with a sampling period of 512 micro seconds in case of trip by LSI or G or optional protections. Within the 5 cycles of the waveform capture, there 4 cycles before the trip event and 1 cycle after the trip event. The record can be retrieved with the Smartphone and EcoStruxure Power Device in Comtrade format. In addition the wave form capture function records the circuit breaker open/close/trip and signal ZSI out. The benefit is the automatic recording of waveform, which helps to analyze the trip event in detail. At a glance, it helps to understand the nature and the gravity of the trip event (with amplitude and duration) and the potential damage on the installation.- Country of Origin
- FR
- Part Number
- LV850003
- Tariff Code
- 85365080
- EAN
- 3606481156235
- UNSPSC
- 39121601
- Consigue plazos de pago de hasta 90 días de 500+ proveedores.
- Descuentos de reventa de hasta el 40%!
Enviar solicitud de precio
1
Formas de pago:
Specifications
- Range Compatibility
- Masterpact (MasterPact MTZ1) circuit breaker || Masterpact (MasterPact MTZ2) circuit breaker || Masterpact (MasterPact MTZ3) circuit breaker
- Application Program Desc
- trip fault WFC
- Service Description
- sampling period of 512 micro seconds in case of trip of LSI or G protection || allows to log automatically five cycles of phase and neutral currents || records the following status: circuit breaker open/closed/trip and ZSI signals || display one cycle before the fault and 4 cycles after
- Energy Management
- diagnostics and maintenance ,crisis management (option)
- Product Or Component Type
- application
- Service Benefits
- help to understand the potential damage on the installation || support analysis of global behaviour of the circuit breaker in the power system || help to understand the nature and gravity of the fault (amplitude and duration)
- Range
- Masterpact
Complementary
- Software Name
- EcoStruxure Power Device
Offer Sustainability
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Eu Rohs Directive
- Compliant
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Otras categorías
ActuadoresBloquesCables, tuberías y manguerasCompresoresControlAcoplamientos y AccesoriosCilindros y PistonesElectrónicaFiltrosHVACPCs industriales y HMIsIluminaciónTécnica linealMotoresFuente de alimentaciónTransmisión de energíaBombas y VálvulasEnergías renovablesRobóticaSellos, anillos y conectoresSensores y dispositivos de mediciónHerramientas y AccesoriosCNCOtros