Descripción

Activo maduro
QO Load Centers offer premium features by allowing QO breakers, ground fault interrupters, arc fault interrupters, and surge arresters to be installed inside. QO Load Centers are designed for residential and industrial use to protect electrical systems, equipment, and people. They are available in both traditional and plug on neutral configurations. There is 3 types of mains available. There is main circuit breaker, main lugs, and generator panel. Single and three phase options are available. The bus bars are tin plated copper and are shielded. Indoor and outdoors enclosures are an option. QO Load Centers enable the use of a full complement of accessories. This 3 phase load center has 30 spaces and 30 circuits. This system provides 200A fixed main lugs in a NEMA 3R enclosure. It also includes a ground bar, and is UL rated.
Country of Origin
US
Part Number
QO330L200GRB
Tariff Code
8537109150
EAN
39121101
UPC
785901295525
UNSPSC
39121101
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.

Environment

Product Certifications
UL Listed
Nema Degree Of Protection
NEMA 3R outdoor
Ambient Air Temperature For Operation
-5 °C || 40 °C

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2212001
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Height
758 mm
Tightening Torque
main lugs 250 lb.in, AWG 4...250 kcmil, aluminium/copper
[Ue] Rated Operational Voltage
208Y/120 V AC || 240/120 V delta AC || 240 V delta AC
Electrical Connection
lugs
Number Of Circuits
30
Number Of Spaces
30
Phase
3 phase
Short-Circuit Current
65 kA
Number Of Tandem Circuit Breakers
0
Material
tin plated copper: busbar
Surface Finish
baked enamel Gray
Line Rated Current
200 A
Enclosure Material
welded galvannealed steel
Awg Gauge
AWG 6...300 kcmil aluminium/copper
Width
375 mm
Wiring Configuration
3-wire || 4-wire
Load Center Type
Fixed Mains (lugs)
Device Composition
grounding bar included (not installed)
Box Number
6R

Specifications

Range Of Product
QO
Product Or Component Type
Load Center
Enclosure Type
weatherproof enclosure
Cover Type
surface cover

Documentos

Data Sheet