- Voltage Range
- 183...484 V
- Safety Reliability Data
- B10d = 850000 || MTTFd = 924.6 years
- Minimum Switching Current
- 10 mA 5 V DC
- Control Circuit Voltage Limits
- 12 % + 10 % Un
- Insulation Resistance
- > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
- Operating Rate
- <= 360 operations/hour full load
- Power Consumption In Va
- 0-22 VA 400 V AC 50 Hz
- Output Contacts
- 2 C/O
- Voltage Detection Threshold
- < 100 V AC
- Marking
- CE
- Response Time
- <= 130 ms (in the event of a fault)
- Operating Position
- any position without derating
- Utilisation Category
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
- Net Weight
- 0.13 kg
- Maximum Switching Voltage
- 250 V AC || 250 V DC
- Measurement Voltage Limits
- 183-484 V AC
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 400 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 183-484 V AC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for relay ON LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Control Circuit Frequency
- 50...60 Hz +/- 10 %
- Width
- 17.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Electrical Durability
- 10000 cycles
- Run-Up Delay At Power-Up
- 650 ms
- Supply Frequency
- 50/60 Hz +/- 10 %