Phoenix Contact
2900575
1 / 1
Description
Hybrid motor starter for reversing 3~ AC motors up to 550 V AC, with 230 V AC input, 2.4 A output current, and adjustable overload shutdown.- Country of Origin
- DE
- Part Number
- 2900575
- Tariff Code
- 85371098
- EAN
- 4046356528177
- UPC
- 4046356528177
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Motor starter/Motor starter combination
- Class Code : EC001037
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Input data
- Input name
- Control input right/left
- Rated actuating voltage UC
- 230 V AC
- Triggering voltage range
- 85 V AC - 253 V AC
- Rated actuating current IC
- 7 mA (Input type 1)
- Mains frequency
- 50/60 Hz
- Switching threshold
- 44 V AC ('0' signal)
- Switching threshold
- 85 V AC ('1' signal)
- Typical turn-off time
- < 70 ms
Dimensions
- Width
- 22.5 mm
- Height
- 107 mm
- Depth
- 114 mm
Connection data 2
- Connection name
- Load circuit
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
- Torque
- 0.5 Nm - 0.6 Nm
- Torque
- 5 lbf-in. - 7 lbf-in.
Connection data
- Connection name
- Control circuits
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
- Torque
- 0.5 Nm - 0.6 Nm
- Torque
- 5 lbf-in. - 7 lbf-in.
Insulation characteristics
- Rated insulation voltage
- 500 V
- Rated surge voltage
- 4 kV
- Overvoltage category
- III
- Degree of pollution
- 2
- Designation
- Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
- Insulation
- Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
- Insulation
- Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
- Insulation
- Basic isolation (IEC 60947-1) at operating voltage 300 - 500 V AC
- Insulation
- Safe isolation (EN 50178) at operating voltage 300 - 500 V AC
- Designation
- Isolation characteristics between the control input and control supply voltage to auxiliary circuit
- Insulation
- Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
- Insulation
- Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Device supply
- Rated control circuit supply voltage US
- 230 V AC
- Control supply voltage range
- 85 V AC - 253 V AC
- Rated control supply current IS
- 4 mA
- Mains frequency
- 50/60 Hz
- Type of protection
- Surge protection
Output data reply output
- Output name
- Acknowledge output
- Note
- Confirmation: floating change-over contact, signal contact
- Contact type
- 1 PDT
- Switching capacity according to IEC 60947-5-1
- 3 A (230 V, AC15)
- Switching capacity according to IEC 60947-5-1
- 2 A (24 V, DC13)
Ambient conditions
- Ambient temperature (operation)
- -25 °C - 70 °C (observe derating)
- Ambient temperature (storage/transport)
- -40 °C - 80 °C
- Maximum altitude
- ≤ 2000 m
- Degree of protection
- IP20
UL data
- SCCR
- 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
- SCCR
- 5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
- FLA
- 2.4 A (500 V AC)
- Group installation
- 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
- Group installation
- 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
- Category code
- NLDX / NRNT
Conformance/approvals
- Designation
- UL approval
- Certificate
- NLDX.E228652
Output data load output
- Output name
- AC output
- Rated operating voltage Ue
- 500 V AC
- Operating voltage range
- 42 V AC - 550 V AC
- Rated operating current Ie
- 2.4 A (AC-51)
- Rated operating current Ie
- 2.4 A (AC-53a)
- Mains frequency
- 50/60 Hz
- Load current range
- 180 mA - 2.4 A (see to derating)
- Trigger characteristic in acc. with IEC 60947-4-2
- Class 10A
- Cooling time
- 20 min. (for auto reset)
- Leakage current
- 0 mA
- Type of protection
- Surge protection
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Standards and Regulations
- Designation
- Standards/regulations
- Standards/regulations
- IEC 60947-1
- Standards/regulations
- IEC 60947-4-2
- Standards/regulations
- IEC 61508
- Standards/regulations
- ISO 13849