Phoenix Contact
2968551
1 / 1
Description
VARIOFACE output module, 32 channels for Yokogawa ADV 551, ADV 561 output modules.- Country of Origin
- DE
- Part Number
- 2968551
- Tariff Code
- 85364190
- EAN
- 4046356418492
- UPC
- 4046356418492
- ETIM
- Group Code : EG000024
- Group Description : PLC's
- Class Description : Interface module
- Class Code : EC002780
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Input data
- Nominal input voltage UN
- 24 V DC ±10 %
- Input voltage range in reference to UN
- 0.9 - 1.1
- Typical input current at UN
- 9 mA (K1 – K32)
- Typical response time
- 5 ms (K1 – K32)
- Typical response time
- 5 ms (K33)
- Typical release time
- 7 ms (K1 – K32)
- Typical release time
- 5 ms (K33)
- Operating voltage display
- Green LED
Supported controller
- Controller
- YOKOGAWA CS3000 CentumVP
- Suitable I/O card
- ADV551
- Suitable I/O card
- ADV561
- Controller
- YOKOGAWA STARDOM
- Suitable I/O card
- NFDV551
- Suitable I/O card
- NFDV561
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
- Type of note
- Notes on operation
- Note
- Do not connect adjacent channels to SELV/ PELV and voltages dangerous to the touch.
- Note
- No additional touch protection is required when using a SELV/PELV voltage (≤ 25 V AC or 60 V DC).
- Note
- At least one functional insulation against adjacent modules is complied with (in the support rail direction). If the application has stricter requirements for the insulation (basic insulation or reinforced insulation), they must be realized by applying suitable measures (e. g. partition plates).
Dimensions
- Width
- 419.5 mm
- Height
- 127.5 mm
- Depth
- 57 mm
Connection data 2
- Connection name
- Controller level
- Connection method
- Yokogawa KS-compatible
- Number of connections
- 2
- Number of positions
- 50
- Note
- Usable system cables: Phoenix Contact YUC50, Yokogawa AKB331
- Torque
- 0.5 Nm
Connection data
- Connection name
- Field level
- Connection method
- Spring-cage connection with disconnect knife
- Number of connections
- 1
- Conductor cross section solid
- 0.2 mm² - 4 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 12
Output data
- Contact type
- 1 PDT
- Contact material
- AgSnO₂
- Maximum switching voltage
- 250 V AC/DC
- Minimum switching voltage
- 12 V AC/DC
- Limiting continuous current
- 2.8 A (observe derating)
- Min. switching current
- 10 mA
- Interrupting rating (ohmic load) max.
- 67 W (24 V DC)
- Interrupting rating (ohmic load) max.
- 20 W (48 V DC)
- Interrupting rating (ohmic load) max.
- 18 W (60 V DC)
- Interrupting rating (ohmic load) max.
- 23 W (110 V DC)
- Interrupting rating (ohmic load) max.
- 40 W (220 V DC)
- Interrupting rating (ohmic load) max.
- 700 VA (250 V AC)
- Output fuse
- 4 A (per channel)
Ambient conditions
- Ambient temperature (operation)
- -15 °C - 50 °C
- Ambient temperature (storage/transport)
- -20 °C - 70 °C
- Maximum altitude
- ≤ 2000 m
- Degree of protection
- IP00
- Degree of protection
- ≥ IP54 (Installation location)
Environmental Product Compliance
- REACh SVHC
- Cadmium oxide 1306-19-0
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Standards and Regulations
- Designation
- Air clearances and creepage distances between the power circuits
- Standards/regulations
- DIN EN 50178
- Rated insulation voltage
- 250 V AC
- Rated surge voltage
- 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths)
- Insulation
- Basic insulation
- Pollution degree
- 2
- Overvoltage category
- III
CAD Models