Need more information?

Call us at:+48 17 778 34 19

ABB 1SFL587002R1211AF305-30-11-12 Contactor

1 / 2
1SFL587002R1211 ABB, PLCs
Reference Image - Not actual item!
1SFL587002R1211 ABB, PLCs
1SFL587002R1211 ABB, PLCs
1SFL587002R1211 ABB, PLCs

Offer Description

The AF305-30-11-12 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 160 kW / 400 V AC (AC-3) or 250 hp / 480 V UL and switching power circuits up to 500 A (AC-1) or 400 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.AF305-30-11-12 Contactor ABB 1SFL587002R1211

Product Description

The AF305-30-11-12 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 160 kW / 400 V AC (AC-3) or 250 hp / 480 V UL and switching power circuits up to 500 A (AC-1) or 400 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

Product Details

Brand
ABB
Country of Origin
SE
Part Number
1SFL587002R1211
Tariff Code
85364900
EAN
7320500481745
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, AC switching
Class Code : EC000066
Version : 7
$1,556.58
excl. tax
Free Shipping!

Offer details

Best offer from:
Trusted Automa.Net Supplier
Availability:
3 pcs.
In-Stock
Updated at: 13-07-2025
Warranty:
12 months
Estimated Delivery:
18-23 July to United States
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
The Seller is responsible for shipping the product and invoicing

Are you a Supplier?

Join 650 suppliers, sell to 3500+ verified buyers.

Sign up now

Policies and Information

Shipping Information

Return & Refund Policies

Secure Payment Process

Warranty Policies

Dimensions

Product Net Width
140 mm
Product Net Depth / Length
180 mm
Product Net Height
225 mm
Product Net Weight
3.9 kg

Technical

Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 500 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 375 A(1000 V) 55 °C 325 A(1000 V) 60 °C 325 A(1000 V) 70 °C 260 A(690 V) 40 °C 500 A(690 V) 55 °C 400 A(690 V) 70 °C 325 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 305 A(440 V) 55 °C 305 A(500 V) 55 °C 290 A(690 V) 55 °C 290 A(1000 V) 55 °C 131 A(380 / 400 V) 55 °C 305 A(220 / 230 / 240 V) 55 °C 305
Rated Operational Power AC-3 (Pe)
(415 V) 160 kW(440 V) 160 kW(500 V) 200 kW(690 V) 250 kW(1000 V) 185 kW(380 / 400 V) 160 kW(220 / 230 / 240 V) 90 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 500 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2440 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 996 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3050 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1409 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4600 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3800 A
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 500 A(220 V) 2 Poles in Series, 40 °C 500 A(220 V) 3 Poles in Series, 40 °C 500 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 400 A(220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 400 A(220 V) 3 Poles in Series, 40 °C 400 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 17 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 17 V·AHolding at Max. Rated Control Circuit Voltage DC 2.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 340 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 340 V·APull-in at Max. Rated Control Circuit Voltage DC 360 W
Operate Time
Between Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main Circuit
Flexible 2 x 70 ... 185 mm²Rigid Al-Cable 1 x 185 ... 240 mm²Rigid Cu-Cable 2 x 70 ... 185 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 1x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars

Eco Transparency

Environmental Product Declaration - EPD
1SFC100104D0201

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3706483
E-Number (Norway)
4117652
E-Number (Sweden)
3210162

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Circular Value

ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 76.3 %
End of Life Instructions
1SFC100112M0001
Group Waste to Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
Improved Resource Efficiency for Customers
Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Sustainable Material Content
Recycled Metal - 33 %

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(600 V AC) 400 A
Horsepower Rating UL/CSA
(200 V AC) Three Phase 100 hp(208 V AC) Three Phase 100 hp(220 ... 240 V AC) Three Phase 125 hp(440 ... 480 V AC) Three Phase 250 hp(550 ... 600 V AC) Three Phase 300 hp

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900