Phoenix Contact
2864752
1 / 1
Description
The item is temporarily not available. The download area includes a conversion table so you can find a suitable replacement item.MCR repeater power supply with spring-cage connection, input signal: (0)4...20 mA, output signal: (0)4...20 mA- Country of Origin
- DE
- Part Number
- 2864752
- Tariff Code
- 85437090
- EAN
- 4017918974954
- UPC
- 4017918974954
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 21-10-2024
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Input data
- Description of the input
- Current input (sensor circuit)
- Number of inputs
- 1
- Current input signal
- 4 mA - 20 mA (repeater power supply and isolator operation)
- Current input signal
- 0 mA - 20 mA (isolator operation)
- Max. input current
- 28 mA
- Input resistance current input
- approx. 50 Ω
- Transmitter supply voltage
- UB - max. 4.5 V for load 0 mA - 20 mA
- Transmitter supply voltage range
- 14.7 V DC - 25.5 V DC
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 6.2 mm
- Height
- 93.1 mm
- Depth
- 102.5 mm
Connection data
- Connection method
- Spring-cage connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Stripping length
- 8 mm
Output data
- Output name
- Current output
- Number of outputs
- 1
- Current output signal
- 4 mA - 20 mA (repeater power supply and isolator operation)
- Current output signal
- 0 mA - 20 mA (isolator operation)
- Max. output current
- 28 mA
- Load/output load current output
- ≤ 500 Ω (I = 20 mA)
- Ripple
- < 20 mVrms (at 500 Ω)
- Transmission Behavior
- 1:1 to input signal
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
Environmental Product Compliance
- China RoHS
- Environmentally Friendly Use Period = 50
- China RoHS
- For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Typical deviation from the measuring range final value
- 10 %
- Designation
- Fast transients (burst)
- Standards/regulations
- EN 61000-4-4
- Typical deviation from the measuring range final value
- 10 %
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Typical deviation from the measuring range final value
- 10 %
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 50081-2
- Connection in acc. with standard
- CUL
- Standards/regulations
- EN 61000-4-2
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Standards/regulations
- EN 61000-4-4
- Standards/regulations
- EN 61000-4-5
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Electrical isolation
- Basic insulation according to EN 61010
- Conformance
- CE-compliant
- ATEX
- II 3 G Ex nA IIC T4 Gc X
- UL, USA/Canada
- UL 508 Recognized
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D T5
- GL
- GL EMC 2 D
- Fire protection for rail vehicles (DIN EN 45545-2) R22
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R23
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R24
- HL 1 - HL 2
Power supply
- Nominal supply voltage
- 24 V DC
- Supply voltage range
- 19.2 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Power consumption
- < 900 mW (at 24 V DC and in repeater power supply operation)
- Power consumption
- < 600 mW (at 24 V DC and in isolator operation)