- Contact type
- 5 enabling current paths
- Contact type
- 1 signaling current path
- Contact material
- AgSnO2
- Maximum switching voltage
- 250 V AC/DC (Observe the load curve)
- Minimum switching voltage
- 5 V AC/DC
- Limiting continuous current
- 6 A (N/O contact, pay attention to the derating)
- Limiting continuous current
- 6 A (N/C contact)
- Maximum inrush current
- 20 A (Δt 100 ms, undelayed contacts)
- Maximum inrush current
- 8 A (delayed contacts)
- Inrush current, minimum
- 10 mA
- Sq. Total current
- 55 A2 (observe derating)
- Interrupting rating (ohmic load) max.
- 144 W (24 V DC, τ = 0 ms)
- Interrupting rating (ohmic load) max.
- 288 W (48 V DC, τ = 0 ms)
- Interrupting rating (ohmic load) max.
- 110 W (110 V DC, τ = 0 ms, delayed contacts: 77 W)
- Interrupting rating (ohmic load) max.
- 88 W (220 V DC, τ = 0 ms)
- Interrupting rating (ohmic load) max.
- 1500 VA (250 V AC, τ = 0 ms, delayed contacts: 2000 VA)
- Maximum interrupting rating (inductive load)
- 42 W (24 V DC, τ = 40 ms, delayed contacts: 48 W)
- Maximum interrupting rating (inductive load)
- 42 W (48 V DC, τ = 40 ms, delayed contacts: 40 W)
- Maximum interrupting rating (inductive load)
- 42 W (110 V DC, τ = 40 ms, delayed contacts: 35 W)
- Maximum interrupting rating (inductive load)
- 42 W (220 V DC, τ = 40 ms, delayed contacts: 33 W)
- Switching capacity min.
- 50 mW
- Mechanical service life
- 10x 106 cycles
- Switching capacity (360/h cycles)
- 4 A (24 V DC)
- Switching capacity (360/h cycles)
- 4 A (230 V AC)
- Output fuse
- 10 A gL/gG (N/O contact)
- Output fuse
- 6 A gL/gG (N/C contact)