1 / 1
thumbnail

Description

Active Mature
This toroid is dedicated to Vigilohm Insulation Fault locators, and to VigiPacT type A residual current protection and monitoring relays. It allows the monitoring of the injected component from Vigilohm Insulation Monitor, and the measurement of a current rating up to 400A for VigiPacT monitoring and protection relays. The transformer ratio is 1/1000. The inner diameter of the toroid is 200 millimeters and the weight is 1.320kg. The cables must be centered within the toroid and the diameter represented by all these cables should not exceed 100 millimeters. The maximum cross section per phase (R, S, T, N) is 2 cables of 185mm² for a copper conductor.
Country of Origin
FR
Part Number
50441
Tariff Code
85043180
EAN
3303430504412
UNSPSC
39121603
€169.12
net
Shipping from:
€25.00
1
Payment methods:
Best offer from:
ITTrusted Automa.Net Supplier
Availability:
9 pcs.
In-Stock
Updated at: 22-11-2024
Warranty:
12 months
Estimated Delivery:
26-29 November to United Kingdom
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environment

Product Certifications
CE
Ambient Air Temperature For Operation
-35-70 °C
Standards
IEC 60947-2
Environmental Characteristic
exposure to damp heat not in service 25...55 °C, RH 95 %) 28 cycles IEC 60068-2-30 || salt mistKb/2 IEC 60068-2-52 || exposure to damp heat in servicecategory C2 48 hours IEC 60068-2-56
Pollution Degree
level 3 IEC 60664-1
Ambient Air Temperature For Storage
-55-85 °C
Ip Degree Of Protection
connectors IP20 || IP30

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2310022EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2310022EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Mounting Mode
fixed cables) || fixed plain backplate) || fixed profiled sheet metal) || fixed slotted backplate)
Network Frequency
45...440 Hz
Height
256 mm
Residual Short-Circuit Withstand Current
85 kA / 0.5 s IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage
12 kV
Network Type
AC/DC
[Ui] Rated Insulation Voltage
1000 V
Connections - Terminals
screw connection 0.22-0.22 mm²
Net Weight
1.32 kg
Cable Outer Diameter
100-100 mm 2 185-185 mm²
Calorific Value
7.05 MJ
Width
274 mm
Overvoltage Category
IV
Depth
46 mm
[Icw] Rated Short-Time Withstand Current
85 kA 0.5 s
Diameter
inner 196 mm
Transformer Ratio
1/1000

Specifications

Range Compatibility
VigiPacT RH10M residual current protection relay || VigiPacT RH10P residual current protection relay || VigiPacT RH21M residual current protection relay || VigiPacT RH21P residual current protection relay || VigiPacT RH68M residual current protection relay || VigiPacT RH86M residual current protection relay || VigiPacT RH86P residual current protection relay || VigiPacT RH99M residual current protection relay || VigiPacT RH99P residual current protection relay || VigiPacT RH197M residual current protection relay || VigiPacT RH197P residual current protection relay || VigiPacT RHU residual current protection relay || VigiPacT RHUs residual current protection relay || VigiPacT RMH residual current protection relay
Product Or Component Type
earth leakage current sensor
Range
VigiPacT
[Ie] Rated Operational Current
400 A
Current Transformer Type
A type closed toroid
Device Application
equipment monitoring and control
Device Short Name
SA200