Schneider Electric
ABLM1A24025
1 / 6
Description
Active Mature
This ABLM regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 240V AC, a rated output current of 2,5A at 24V DC and a rated power output of 60W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. It installs on omega rail or fixing by screw. Its width is 53mm, its height is 91mm, its depth is 55,6mm. It ensures a protection against overloads and short-circuits with automatic restart after the source of overload/short-circuit has been corrected. It weighs 0.221kg. It is a power supply for industrial use, rail mounting. It conforms to EN62368-1, ENIEC61010-1/2-201, ENIEC61204-3, EN61000-6-1/2/3/4, EN61000-3-2-3, UL62368-1, UL61010-2-201/-1-201, CSAC22.2No62368-1/No61010-2-201/No61010-1 standards, and certified by CE, CUL listed/recognized, RCM, CBscheme. The Acti9 iC60 range of Miniature Circuit Breakers is recommanded for its protection. The type of protection is 6A, C curve or 10A, B-curve. It has in the front face a LED indicating presence of DC output voltage, and a QR code for access to the latest technical documentation. Thanks to their modular housing, they can be installed either in enclosures or industrial panels by clipping on omega (DIN) rail. It brings energy to your automated systems. Designed for simple machines and applications, modular power supplies are primarily appreciated for their extreme compactness.- Country of Origin
- TH
- Part Number
- ABLM1A24025
- Tariff Code
- 85044083
- EAN
- 3606481500175
- UNSPSC
- 39121004
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 278 pcs.In-StockUpdated at: 22-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Complementary
- Output Coupling
- serial || parallel
- Height
- 91 mm
- Residual Ripple
- < 100 mV
- Status Led
- 1 LED (Green) output voltage
- Holding Time
- > 20 ms 115 V AC || > 60 ms 230 V AC
- Efficiency At Full Load
- 90...264 V AC
- Earthing System
- TN || TT || IT
- Connections - Terminals
- screw connection 0.5...2.5 mm², AWG 20...AWG 14) without wire end ferrule output || screw connection 0.5...1.5 mm², AWG 20...AWG 16) with wire end ferrule output || screw connection 0.5...1.5 mm², AWG 20...AWG 16) input
- Dielectric Strength
- 3000 V AC input/output
- Network Frequency Limits
- 50-60 Hz
- Current Consumption
- < 1.5 A 115 V AC || < 1 A 230 V AC
- Supply
- SELV IEC 60950-1 || SELV IEC 60204-1 || SELV IEC 60364-4-41
- Net Weight
- 0.221 kg
- Maximum Leakage Current
- 0.25 mA 240 V AC
- Input Protection Type
- integrated fuse (not interchangeable) 3.15 A || external protection (recommended) 20 A Curve B || external protection (recommended) 20 A Curve C || external protection (recommended) 10 A Curve B || external protection (recommended) 6 A Curve C
- Output Protection Type
- against overload and short-circuits automatic reset || against over temperature manual reset || against overvoltage manual reset
- Service Life
- 10 year(s)
- Meantime Between Failure [Mtbf]
- 1300000 h at 25 °C, full load || 700000 h at 55 °C, 80 % load
- Power Dissipation In W
- 6.5 W
- Output Voltage Limits
- 24...28 V
- Mounting Support
- top hat type TH35-15 rail IEC 60715 || top hat type TH35-7.5 rail IEC 60715 || double-profile DIN rail || panel mounting
- Load Capacitance
- 3000 µF
- Response Time
- < 2 s
- Line And Load Regulation
- < 0.5 % network in line || < 1 % network 0 to 100 % load
- Width
- 53 mm
- Overvoltage Category
- II
- Inrush Current
- 30 A 115 V || 60 A 230 V
- Efficiency
- 90 % 115 V AC || 90 % 230 V AC
- Depth
- 55.6 mm
- Power Factor
- 0.50 at 115 V AC || 0.39 at 230 V AC
Specifications
- Range Of Product
- Modicon Power Supply
- Output Voltage
- 24 V DC
- Product Or Component Type
- power supply
- Power Supply Type
- regulated switch mode
- Input Voltage
- 100...240 V AC single phase || 100...240 V AC phase to phase
- Power Supply Output Current
- 2.5 A
- Kw Rating
- 60 W
- Enclosure Material
- Plastic
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2004005EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI2004005EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Environment
- Standards
- IEC 62368-1 || EN/IEC 61010-1 || EN 61010-2-201 || EN/IEC 61204-3 || IEC 61000-6-1 || IEC 61000-6-2 || IEC 61000-6-3 || IEC 61000-6-4 || IEC 61000-3-2 || EN 61000-3-3 || UL 62368-1 || UL 61010-1 || UL 61010-2-201 || CSA C22.2 No 62368-1 || CSA C22.2 No 61010-1 || CSA C22.2 No 61010-2-201 || EN/IEC 62368-1
- Ambient Air Temperature For Operation
- -25--10 °C with current derating of 1 % per °C mounting position A < 6561.68 ft (2000 m) || -10-55 °C without current derating mounting position A < 6561.68 ft (2000 m) || 55-70 °C with current derating of 2.67 % per °C mounting position A < 6561.68 ft (2000 m)
- Product Certifications
- CE || cUL Listed || cUL Recognized || RCM || CB Scheme || EAC || KC || NEC class 2
- Pollution Degree
- 2
- Electromagnetic Compatibility
- immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2 || immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2 || electromagnetic field immunity test - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3 || electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3 || electromagnetic field immunity test - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3 || immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4 || surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5 || surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5 || immunity to conducted disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6 || immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 || immunity to voltage dips - test level: 100 % (1 cycle) conforming to IEC 61000-4-11 || immunity to voltage dips - test level: 60 % (10 cycles) conforming to IEC 61000-4-11 || immunity to voltage dips - test level: 30 % (25 cycles) conforming to IEC 61000-4-11 || disturbing field emission conforming to EN 55016-2-3 || limits for harmonic current emissions conforming to IEC 61000-3-2 || conforming to EN 55016-1-2 || conforming to EN 55016-2-1
- Shock Resistance
- 150 m/s² 11 ms
- Vibration Resistance
- 3 mm 2-9 Hz)IEC 60721-3-3 || 10 m/s² 9-200 Hz)IEC 60721-3-3
- Ip Degree Of Protection
- IP20
- Operating Altitude
- < 6561.68 ft (2000 m) overvoltage category III || 2000 m...5000 m overvoltage category II
- Electrical Shock Protection Class
- class II without PE connection
- Electromagnetic Emission
- conducted emissions IEC 61000-6-3 || radiated emissions IEC 61000-6-4
CAD Models
traceparts
Download