Need more information?
Call us at:+48 17 778 34 19
Schneider Electric BMXDRA1605 discrete output module, Modicon X80, 16 NO relay outputs, 24 to 240V AC, 24 to 48V DC
1 / 6
Offer Description
OUTPUT MODULE 8 RELAY OUTPUTS M340 SERIES 24 VDC PLUG-IN MOUNTING IP20 Schneider BMXDRA1605
Product Description
Active Mature
This discrete output module is part of the Modicon X80 modules. It has 16 relay non protected outputs, 24V DC / 24V to 240V AC. This module is connected via 20-way removable terminal block. It occupies a single slot on the rack and it has a case which provides IP 20 protection of the electronics.
Product Details
- Country of Origin
- FR
- Part Number
- BMXDRA1605
- Tariff Code
- 85389099
- EAN
- 3595863909234
- UNSPSC
- 32151706
$1,200.00
excl. tax1
Offer details
- Best offer from:
Trusted Automa.Net Supplier
- Availability:
- 10 pcs.In-StockUpdated at: 20-03-2025
- Warranty:
- 12 months
- Estimated Delivery:
- 27 March - 01 April to United States
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
The Seller is responsible for shipping the product and invoicing
Are you a Supplier?
Join 650 suppliers, sell to 3500+ verified buyers.
Policies and Information
Shipping Information
Return & Refund Policies
14 days for return
Secure Payment Process
Warranty Policies
Environment
- Ambient Air Temperature For Operation
- 0-60 °C
- Shock Resistance
- 30 gn
- Dielectric Strength
- 2000 V AC 50/60 Hz 1 min
- Vibration Resistance
- 3 gn
- Ambient Air Temperature For Storage
- -40-85 °C
- Relative Humidity
- 5-95 % 55-55 °C without condensation
- Operating Altitude
- 0...6561.68 ft (0...2000 m) || 2000...5000 m with derating factor
- Ip Degree Of Protection
- IP20
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Mtbf Reliability
- 2100000 H
- Minimum Switching Current
- 1 mA 5 V DC
- Status Led
- 1 LED (Green) RUN || 1 LED per channel (Green) channel diagnostic || 1 LED (Red) ERR || 1 LED (Red) I/O
- Insulation Resistance
- > 10 MOhm 500 V DC
- [Ith] Conventional Free Air Thermal Current
- 2 A
- Power Dissipation In W
- 3 W
- Net Weight
- 0.15 kg
- Electrical Durability
- AC-15 100000 cycles 240 VA 200 V 0.7 ) || AC-15 100000 cycles 120 VA 200 V 0.35 ) || AC-12 100000 cycles 200 VA 100 V || AC-12 100000 cycles 80 VA 48 V || AC-12 100000 cycles 50 VA 24 V || AC-15 100000 cycles 120 VA 100 V || AC-15 100000 cycles 120 VA 24 V || AC-15 100000 cycles 120 VA 48 V || DC-12 100000 cycles 24 W 24 V || DC-13 100000 cycles 10 W 24 V || DC-13 100000 cycles 10 W 48 V || AC-15 300000 cycles 72 VA 200 V 0.7 ) || AC-15 300000 cycles 36 VA 200 V 0.35 ) || AC-12 300000 cycles 200 VA 200 V || AC-12 300000 cycles 80 VA 100 V || AC-12 300000 cycles 50 VA 48 V || AC-15 300000 cycles 36 VA 100 V || AC-15 300000 cycles 72 VA 100 V || AC-15 300000 cycles 36 VA 48 V || AC-15 300000 cycles 72 VA 48 V || AC-15 300000 cycles 36 VA 24 V || AC-15 300000 cycles 72 VA 24 V || DC-13 300000 cycles 3 W 24 V || DC-13 300000 cycles 3 W 48 V || DC-13 7000 cycles 24 W 24 V || DC-13 7000 cycles 24 W 48 V || DC-12 50000 cycles 24 W 48 V
- Typical Current Consumption
- 100 mA 3.3 V DC || 95 mA 24 V DC
- Output Overvoltage Protection
- use discharge diode on each output DC || use RC circuit on each output AC || use ZNO surge limiter on each output AC
- Output Short-Circuit Protection
- use 1 fast blow fuse per channel or group of channel
- Output Overload Protection
- use 1 fast blow fuse per channel or group of channel
- Response Time On Output
- < 8 ms activation || < 10 ms deactivation
Specifications
- Discrete Output Type
- relay
- Range Of Product
- Modicon X80
- Discrete Output Number
- 16 EN/IEC 61131-2
- Discrete Output Voltage
- 24...48 V 19...60 V DC || 24...240 V 19…264 V AC
- Product Or Component Type
- discrete output module