- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- Power Dissipation Per Pole
- 2 W AC-3 || 5 W AC-1 || 2 W AC-3e
- Average Impedance
- 2 mOhm - Ith 50 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 10 A (at 60 °C) for signalling circuit || 50 A (at 60 °C) for power circuit
- Control Circuit Voltage Limits
- 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
- Mounting Support
- rail || plate
- Contact Compatibility
- M2
- Control Circuit Type
- AC 50/60 Hz
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Rated Breaking Capacity
- 550 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
- Inrush Power In Va
- 70-70 VA 60 Hz cos phi 0.75 (at 20 °C) || 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-10 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 1.5-10 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: solid without cable end
- Coil Technology
- without built-in suppressor module
- Operating Time
- 12...22 ms closing || 4...19 ms opening
- Minimum Switching Voltage
- 17 V for signalling circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
- Electrical Durability
- 1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V
- Mechanical Durability
- 15 Mcycles
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C) || 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 2 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 20 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 25 hp at 575/600 V AC 50/60 Hz for 3 phase motors
- Motor Power Kw
- 7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) || 7.5 kW at 220...230 V AC 50/60 Hz (AC-3e) || 15 kW at 380...400 V AC 50/60 Hz (AC-3e) || 15 kW at 415...440 V AC 50/60 Hz (AC-3e) || 18.5 kW at 500 V AC 50/60 Hz (AC-3e) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
- [Icw] Rated Short-Time Withstand Current
- 260 A 40 °C - 10 s for power circuit || 430 A 40 °C - 1 s for power circuit || 60 A 40 °C - 10 min for power circuit || 138 A 40 °C - 1 min for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
- Heat Dissipation
- 2-3 W at 50/60 Hz
- Protective Cover
- with