Need more information?
Schneider Electric LC1DT40D7
IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 4 NO, 42VAC 50/60Hz coil
Product Description
The TeSys D contactor is engineered for integration into diverse control systems, facilitating motor starter applications across various use cases. This specific model features a configuration of four poles, all normally open, capable of handling resistive loads up to 40A. The contactor is designed with a coil rated at 42VAC for both 50Hz and 60Hz operations.
Dimensions for this unit are 91mm in height, 45mm in width, and 99mm in depth, with a net weight of 0.425 kg. Its structural design allows for mounting on standard DIN rail or direct panel installation. The contactor includes one normally open and one normally closed auxiliary contact, with the NC contact being certified as mirror. It employs screw clamp terminals for efficient load and auxiliary connections, ensuring reliability and ease of installation.
The product meets multiple international standards, including UL, CSA, and IEC certifications, and is classified under various environmental regulations, including RoHS and REACh, marking it as a sustainable choice. The mechanical robustness is validated with a vibration tolerance of 2 Gn while open and 4 Gn while closed, and it withstands shocks of up to 15 Gn. Operating conditions allow for altitudes up to 3000m and ambient temperatures ranging from -40°C to 60°C without derating.
In terms of electrical specifications, the contactor supports a rated breaking capacity of 450A at 440V. Its rated insulation voltage is 600V for the power circuit, and it has a rated...
Need more information?
Offer details
- Offer from:
Trusted supplier — Romania, member since 2023, 1–4 employees
- Availability:
- On requestLead time: 21 days
- Warranty:
- Not specified
- Condition:
- New Surplus
Specifications
- Brand
- Schneider Electric
- Product Certifications
- GL || LROS (Lloyds register of shipping) || CSA || UL || RINA || BV || GOST || DNV || CCC
- Standards
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Climatic Withstand
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Flame Retardance
- V1 conforming to UL 94
- Protective Treatment
- THIEC 60068-2-30
- Ip Degree Of Protection
- IP20 front face IEC 60529
Available Offers
(3)| Condition | Availability | Supplier | Warranty | Action | |
|---|---|---|---|---|---|
| Condition New Surplus | Availability On requestLead time: 21 days | Supplier | Warranty Not specified | ||
| Condition New Factory Sealed | Availability On requestLead time to be confirmed | Supplier | Warranty Not specified | ||
| Condition New Factory Sealed | Availability On requestLead time to be confirmed | Supplier | Warranty 12 months |
Offer with manufacturer lead time
Directly from the manufacturer - with a confirmed, predictable, and fully transparent delivery time.
Documents
Data Sheet
Datasheet for Schneider Electric LC1DT40D7, including specifications and features.
CAD Models
3D CAD model and technical drawings, ready for your design software.
Product data updated: 22-08-2026

Market insights for LC1DT40D7
Get real-time analytics and market data for LC1DT40D7 and similar products to optimize your purchasing decisions
- Real-time stock availability data from 700 MRO distributors in Europe and USA
- Price analysis by condition (new, used, refurbished) with market median prices
- Critical component availability monitoring to prevent production downtime