TeSys D time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 1-30s, connection by screw clamp terminals. A delay of 40ms is ensured between opening of NC contact and closing of NO contact. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).
Country of Origin
FR
Part Number
LADS2
Tariff Code
85365080
EAN
3389110386103
UNSPSC
39121529
£31.50
net
£35.00
Free Shipping!
1
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
2 pcs.
In-Stock
Updated at: 07-11-2024
Warranty:
12 months
Estimated Delivery:
12-13 November to United Kingdom
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environment

Ambient Air Temperature For Operation
-40-70 °C
Ip Degree Of Protection
IP20 conforming to IEC 60529
Ambient Air Temperature For Storage
-60-80 °C
Environmental Characteristic
normal environment
Protective Treatment
TH IEC 60068
Operating Altitude
9842.52 ft (3000 m)

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110702
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer - www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
N/A
Eu Rohs Directive
Compliant with Exemptions

Complementary

Non-Overlap Time
1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
Permissible Short-Time Rating
100 A 60 °C 1 s || 120 A 60 °C 500 ms || 140 A 60 °C 100 ms
Minimum Switching Current
5 mA
Height
48 mm
Protection Type
gG fuse 10 A
Insulation Resistance
> 10 MOhm
Irms Rated Making Capacity
140 A at <= 690 V AC conforming to IEC 60947-5-1 || 250 A at <= 690 V DC conforming to IEC 60947-5-1
Connections - Terminals
screw clamp terminals 1 1-2.5 mm²flexible with cable end || screw clamp terminals 1 1-2.5 mm²flexible without cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible without cable end || screw clamp terminals 1 1-2.5 mm²rigid || screw clamp terminals 2 1-2.5 mm²rigid || screw clamp terminals
Minimum Switching Voltage
17 V
Tightening Torque
1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2
Mechanical Durability
5 Mcycles
Color
dark grey
Width
44 mm
Depth
61 mm

Specifications

Product Certifications
IECEE CB Scheme || UL || CSA || CCC || EAC || UKCA
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C)
Standards
CSA C22.2 No 60947-5-1 || GB/T 14048.5 || EN/IEC 60947-5-1
Timer Type
on delay
[Ue] Rated Operational Voltage
690 V AC 25...400 Hz
Range Compatibility
TeSys Deca CAD || TeSys Deca LC1D || TeSys F LC1F || TeSys F CR1F
Product Or Component Type
time delay auxiliary contact block
Product Name
TeSys Deca
Range
TeSys || TeSys Deca
Mounting Location
front
Pole Contact Composition
1 NO + 1 NC
[Ui] Rated Insulation Voltage
690 V IEC 60947-5-1 || 600 V UL 60947-5-1 || 600 V CSA C22.2 No 60947-5-1
[Ie] Rated Operational Current
6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
Time Delay Range
1...30 s
Auxiliary Contacts Operation
time delay
Device Application
star delta starter

CAD Models

traceparts
traceparts
Download