1 / 1
thumbnail

Description

Active Mature
TeSys F contactor, 3 poles (3NO), 265A/1000V AC-3, for motor applications up to 132kW@400V. It provides a low sealed consumption 110V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Country of Origin
CZ
Part Number
LC1F265F7
Tariff Code
85364900
EAN
3389110351606
UNSPSC
39121529
Payment methods:
Best offer from:
USTrusted Automa.Net Supplier
Availability:
9 pcs.
In-Stock
Updated at: 31-07-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 52 Parts In-Stock from 6 Distributors
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (5)

LC1F265F7 product image
Schneider Electric

LC1F265F7

Condition:
New Factory Sealed
Available:
10 pcs.
In-Stock
Updated at: 22-11-2024
Offer from:
SKTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1F265F7 product image
Schneider Electric

LC1F265F7

Condition:
New Surplus
Available:
4 pcs.
In-Stock
Updated at: 22-11-2024
Offer from:
USTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
$1,573.33
net
LC1F265F7 product image
Schneider Electric

LC1F265F7

Condition:
New Surplus
Available:
27 pcs.
In-Stock
Updated at: 21-11-2024
Offer from:
ITTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1F265F7 product image
Schneider Electric

LC1F265F7

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 21-10-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
1
LC1F265F7 product image
Schneider Electric

LC1F265F7

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 22-11-2024
Offer from:
DETrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
€510.11

Specifications

[Uc] Control Circuit Voltage
110 V AC 40...400 Hz
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 1000 V AC-1 || <= 690 V AC-3 || <= 690 V AC-4 || <= 460 V DC
Contactor Application
resistive load || motor control
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1 || AC-4 || AC-3
[Ie] Rated Operational Current
350 A 40 °C) <= 440 V AC AC-1 || 265 A 55 °C) <= 440 V AC AC-3
Poles Description
3P
Device Short Name
LC1F

Contractual warranty

Warranty
18 months

Complementary

Product Certifications
BV || RINA || CSA || UL || DNV || RMRoS || CB || LROS (Lloyds register of shipping) || ABS || UKCA
Power Dissipation Per Pole
37 W AC-1 || 21 W AC-3
Average Impedance
0.3 mOhm - Ith 350 A 50 Hz
[Ith] Conventional Free Air Thermal Current
350 A 40 °C
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.15...0.2 Uc 40...400 Hz 55 °C)
Standards
EN 60947-4-1 || JIS C8201-4-1 || EN 60947-1 || IEC 60947-1 || IEC 60947-4-1
Mounting Support
plate
Control Circuit Type
AC 40...400 Hz
Contactor Coil Voltage
110 V AC standard
Rated Breaking Capacity
2120 A IEC 60947-4-1
Power Range
55-100 kW 200-240 V 3 phase || 110-220 kW 480-500 V 3 phase || 110-220 kW 380-440 V 3 phase
Associated Fuse Rating
315 A aM <= 440 V || 400 A gG <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
650-650 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 32 x 4 mm || power circuit lugs-ring terminals 1 240-240 mm² || power circuit connector 1 240-240 mm² || power circuit bolted connection
Pole Contact Composition
3 NO
Motor Starter Type
direct on-line contactor
Operating Time
40...65 ms closing || 100...170 ms opening
Maximum Operating Rate
2400 cyc/h 55 °C
Mechanical Durability
10 Mcycles
Tightening Torque
control circuit 1.2 N.m || power circuit 35 N.m
Compatibility Code
LC1F
Hold-In Power Consumption In Va
10-10 VA, 40...400 Hz 0.9 20 °C)
Overvoltage Category
III
Motor Power Kw
132 kW 380...400 V AC 50/60 Hz AC-3) || 140 kW 415 V AC 50/60 Hz AC-3) || 140 kW 440 V AC 50/60 Hz AC-3) || 160 kW 500 V AC 50/60 Hz AC-3) || 160 kW 660...690 V AC 50/60 Hz AC-3) || 147 kW 1000 V AC 50/60 Hz AC-3) || 75 kW 220...230 V AC 50/60 Hz AC-3) || 51 kW 400 V AC 50/60 Hz AC-4)
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
2200 A 40 °C - 10 s || 1230 A 40 °C - 30 s || 950 A 40 °C - 1 min || 620 A 40 °C - 3 min || 480 A 40 °C - 10 min
Heat Dissipation
8-8 W

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP080208EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI100418
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-5-55 °C
Height
203 mm
Net Weight
7.44 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Width
201.5 mm
Depth
213 mm
Permissible Ambient Air Temperature Around The Device
-40-70 °C

CAD Models

traceparts
traceparts
Download