Schneider Electric

LP1K090085MD

1 / 1
thumbnail

Descripción

Activo maduro
TeSys K contactor, 4 poles (2NO+2NC), for non-inductive load control applications up to 20A/690V AC-1. It provides a 220V DC coil, without built-in auxiliary contact, connection by solder pins for printed circuit boards. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Country of Origin
FR
Part Number
LP1K090085MD
Tariff Code
85364900
EAN
3389110496161
UNSPSC
39121529
Métodos de pago:
Mejor oferta de:
ITProveedor de confianza de Automa.Net
Disponibilidad:
1 pieza
En stock
Actualizado en: 09-11-2024
Garantía:
12 meses
Entrega Estimada:
Bajo pedido
Condición:
Nuevo Precintado de Fábrica
Nuevo Precintado de Fábrica - Un artículo completamente nuevo, sin usar, sin abrir, sin daños, en su embalaje original sellado por el fabricante.
Un total de 2 Parts In-Stock de 2 Distributors
Entrega desde:
IT
IT
DE
DE
Información de envío
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Ofertas Disponibles (1)

LP1K090085MD product image
Schneider Electric

LP1K090085MD

Condición:
Nuevos excedentes
Disponible:
1 pieza
En stock
Actualizado en: 08-11-2024
Oferta de:
DEProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
12 meses
1
Oferta con plazo de entrega del fabricante
Entrega:Bajo pedido
El mejor precio:
€13.98

Environment

Product Certifications
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Ambient Air Temperature For Operation
-25-50 °C
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Flame Retardance
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage
-50-80 °C
Ip Degree Of Protection
IP2X
Operating Altitude
6561.68 ft (2000 m) without derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503003EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1503003EN
Eu Rohs Directive
Compliant

Complementary

[Uc] Control Circuit Voltage
220 V DC
[Ue] Rated Operational Voltage
power circuit <= 690 V AC <= 400 Hz || signalling circuit <= 690 V AC <= 400 Hz
Height
58 mm
Average Impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
Control Circuit Voltage Limits
operational: 0.8...1.15 Uc (at <50 °C) || drop-out: >= 0.10 Uc (at <50 °C)
[Ith] Conventional Free Air Thermal Current
20 A (at 60 °C) for power circuit || 10 A (at 50 °C) for signalling circuit
Mounting Support
printed circuit boards
Control Circuit Type
DC standard
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Hold-In Power Consumption In W
3-3 W 20 °C
Rated Breaking Capacity
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
Irms Rated Making Capacity
110 A AC for power circuit conforming to IEC 60947
Motor Power Kw
4 kW 690 V AC 50/60 Hz AC-4
Associated Fuse Rating
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
Net Weight
0.225 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
solder pins 0.035 mm)
Pole Contact Composition
2 NO + 2 NC
Utilisation Category
AC-1
[Ie] Rated Operational Current
20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Maximum Operating Rate
3600 cyc/h
Electrical Durability
0.16 Mcycles 20 A AC-1 <= 690 V
Mechanical Durability
10 Mcycles
Inrush Power In W
3-3 W 20 °C)
Poles Description
4P
Operating Time
30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening || 25...35 ms coil energisation and NC opening || 15 ms coil de-energisation and NC closing
Width
45 mm
Overvoltage Category
III
Depth
57 mm
[Ui] Rated Insulation Voltage
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA C22.2 No 14
[Icw] Rated Short-Time Withstand Current
90 A 50 °C - 1 s for power circuit || 85 A 50 °C - 5 s for power circuit || 80 A 50 °C - 10 s for power circuit || 60 A 50 °C - 30 s for power circuit || 45 A 50 °C - 1 min for power circuit || 40 A 50 °C - 3 min for power circuit || 20 A 50 °C - >= 15 min for power circuit
Heat Dissipation
1.3-1.3 W

Specifications

Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Device Short Name
LP1K

Modelos CAD

traceparts
traceparts