1 / 1
thumbnail

Descripción

TeSys LR9F electronic overload relay, thermal setting range 48-80A, class 20, for protection of motors 30-37kW@400V. to be mounted directly below a TeSys F 3-pole contactor LC1 F115, F150, F185, use of a support mounting plate LA7F901 is recommended (to be ordered separately). Motor protection includes thermal overload of 1-phase and 3-phase motors, phase failure, phase unbalance, prolonged starting times, stalled rotor conditions. On the front of the relay, it provides a thermal adjustement dial, buttons for test, stop & reset, a trip indicator, trip auxiliary contacts 1NO+1NC. Multi standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).
Country of Origin
FR
Part Number
LR9F5563
Tariff Code
85364900
EAN
3389110640175
UNSPSC
39122330
Métodos de pago:
Mejor oferta de:
GBProveedor de confianza de Automa.Net
Disponibilidad:
1 pieza
En stock
Actualizado en: 30-04-2024
Entrega Estimada:
Bajo pedido
Condición:
Nuevo Precintado de Fábrica
Nuevo Precintado de Fábrica - Un artículo completamente nuevo, sin usar, sin abrir, sin daños, en su embalaje original sellado por el fabricante.
Un total de 4 Parts In-Stock de 3 Distributors
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Ofertas Disponibles (2)

LR9F5563 product image
Schneider Electric

LR9F5563

Condición:
Nuevos excedentes
Disponible:
1 pieza
En stock
Actualizado en: 12-11-2024
Oferta de:
DEProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
12 meses
1
LR9F5563 product image
Schneider Electric

LR9F5563

Condición:
Nuevos excedentes
Disponible:
2 piezas
En stock
Actualizado en: 12-11-2024
Oferta de:
ITProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
12 meses
1
Oferta con plazo de entrega del fabricante
Entrega:Bajo pedido
El mejor precio:
€171.11

Specifications

Network Type
AC
Thermal Protection Adjustment Range
48-80 A
Relay Application
motor protection
Product Or Component Type
electronic thermal overload relay
Product Name
TeSys LRF
Thermal Overload Class
class 20 IEC 60947-4
Range
TeSys
Product Compatibility
LC1F115...LC1F185
Device Short Name
LR9F

Contractual warranty

Warranty
18 months

Complementary

Network Frequency
50/60 Hz
Current Consumption
<= 5 mA no-load
Height
96 mm
[Ith] Conventional Free Air Thermal Current
5 A control circuit
Tightening Torque
control circuit 1.2 N.m screw clamp terminals || power circuit 18 N.m screw clamp terminals
Reset
manual reset on front relay
Phase Failure Sensitivity
tripping in 4 s +/- 20 % IEC 60947-4-1
[Ue] Rated Operational Voltage
1000 V AC 50/60 Hz power circuit VDE 0110 group C
Switching Capacity In Ma
0...150 mA
Net Weight
0.9 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947-1
Maximum Voltage Drop
<2.5 V closed state
Connections - Terminals
control circuit screw clamp terminals 1 0.75-2.5 mm² flexible - with cable end || control circuit screw clamp terminals 1 0.75-2.5 mm² solid || control circuit screw clamp terminals 1 0.75-4 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1.5 mm² flexible - with cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1 mm² solid || power circuit lugs-ring terminals M8
[Ui] Rated Insulation Voltage
power circuit 1000 V AC IEC 60947-4
Contacts Type And Composition
1 NO + 1 NC
Surge Withstand
4 kV IEC 61000-4-5
Tripping Threshold
1.12 +/- 0.06 In tripping IEC 60947-4-1
Mounting Support
direct on contactor || plate
Control Type
dial White full-load current adjustment || test button Red || push-button Red reset || push-button stop
Local Signalling
trip indicator
Width
115 mm
Depth
123.5 mm
Temperature Compensation
-20-70 °C

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP080207EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI100406
Eu Rohs Directive
Compliant

Environment

Product Certifications
CSA || UL || UKCA
Mechanical Robustness
shocks13 Gn for 11 ms IEC 60068-2-7 || vibrations 5...300 Hz2 GN IEC 60068-2-6
Standards
IEC 60255-17 || VDE 0660 || IEC 60255-8 || IEC 60947-4-1 || EN 60947-4-1
Ambient Air Temperature For Operation
-20-55 °C IEC 60255-8
Electromagnetic Compatibility
resistance to electrostatic discharge 6 kV in indirect mode IEC 61000-4-2 || resistance to electrostatic discharge 8 kV in air IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test 10 V/m IEC 61000-4-3 || fast transients immunity test 2 kV IEC 61000-4-4
Dielectric Strength
6 kV 50 Hz IEC 255-5
Ip Degree Of Protection
IP20 conforming to IEC 60529 || IP20 conforming to VDE 0106
Ambient Air Temperature For Storage
-40-85 °C
Protective Treatment
TH
Operating Altitude
<= 6561.68 ft (2000 m) without derating
Fire Resistance
850 °C IEC 60695-2-1

Modelos CAD

traceparts
traceparts
Descargar