Schneider Electric
LV847241
1 / 1
- Country of Origin
- FR
- Part Number
- LV847241
- Tariff Code
- 85362090
- EAN
- 3606480816253
- UNSPSC
- 39121601
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Specifications
- Network Frequency
- 50/60 Hz
- Network Type
- AC
- Breaking Capacity Code
- H2
- Product Or Component Type
- circuit breaker
- Product Name
- MasterPact MTZ1
- Range
- Masterpact
- Utilisation Category
- category B
- Suitability For Isolation
- yes IEC 60947-2
- Poles Description
- 3P
- Device Application
- protection
- Device Short Name
- MTZ1 16 H2
Complementary
- [Ics] Rated Service Breaking Capacity
- 50 kA 220/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 440 V AC 50/60 Hz IEC 60947-2 || 42 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 42 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Line Rated Current
- 1600 A 40 °C
- Connection Pitch
- 70 mm
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Mounting Support
- rails || base plate
- Circuit Breaker Ct Rating
- 1250 A || 1600 A || 630 A || 1000 A || 400 A || 800 A
- Maximum Breaking Time
- 25-25 ms
- Depth
- drawout circuit breaker without chassis 207.5 mm || drawout circuit breaker with chassis 266 mm
- Control Type
- push-button
- Maximum Closing Response Time
- 50 ms
- Mounting Mode
- drawout
- Breaking Capacity
- 50 kA Icu 220/415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 42 kA Icu 500/525 V AC 50/60 Hz IEC 60947-2 || 42 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- [Icm] Rated Short-Circuit Making Capacity
- 105 kA 220/415 V AC 50/60 Hz || 105 kA 440 V AC 50/60 Hz || 88 kA 500/525 V AC 50/60 Hz || 88 kA 660/690 V AC 50/60 Hz
- Electrical Durability
- 3000 cycles 690 V AC 50/60 Hz IEC 60947-2 || 6000 cycles 440 V AC 50/60 Hz IEC 60947-2 || AC-23A 3000 cycles 690 V AC 50/60 Hz IEC 60947-3 || AC-23A 6000 cycles 440 V AC 50/60 Hz IEC 60947-3 || AC-3 6000 cycles 440 V AC 50/60 Hz IEC 60947-3
- [Ui] Rated Insulation Voltage
- 1000 V AC 50/60 Hz IEC 60947-2
- Mechanical Durability
- 12500 cycles with periodic preventive maintenance IEC 60947-2
- Height
- drawout circuit breaker without chassis 259.5 mm || drawout circuit breaker with chassis 322 mm
- Width
- drawout circuit breaker without chassis 236.5 mm || drawout circuit breaker with chassis 288 mm
- Integral Instant Protection
- 81-99 kA
- [Uimp] Rated Impulse Withstand Voltage
- 12 kVIEC 60947-2
- [Icw] Rated Short-Time Withstand Current
- 42 kA 0.5 s IEC 60947-2 || 42 kA 1 s IEC 60947-2 || 24 kA 3 s IEC 60947-2
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1706010EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1706010EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- LCIE || ASEFA
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- IEC 60947-2 || IEC 60364-8-1
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -40-85 °C
CAD Models
traceparts
Download