1 / 1
thumbnail

Opis

Końcówka Serii
This Multi9 C60BP is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 10A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard and 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 103mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
Country of Origin
FR
Part Number
M9F42110
Tariff Code
85362010
EAN
3606481169600
UNSPSC
39121603
€27.67
net
€29.13
Darmowa wysyłka!
1
Metody płatności:
Najlepsza oferta od:
NLZaufany dostawca Automa.Net
Dostępność:
8 szt.
W magazynie
Zaktualizowano: 05-11-2024
Gwarancja:
12 miesięcy
Szacowany czas dostawy:
12-15 listopada do Wielka Brytania
Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Fabrycznie Nowe, Zapieczętowane - Nowy, nieużywany, nieotwarty, nieuszkodzony przedmiot w oryginalnym opakowaniu zapieczętowanym przez producenta.
Łącznie 67 części w magazynie od 16 dostawców
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja

Dostępne Oferty (16)

M9F42110 product image
Schneider Electric

M9F42110

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
6 szt.
W magazynie
Zaktualizowano: 07-11-2024
Oferta od:
DEZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€42.53
net
M9F42110 product image
Schneider Electric

M9F42110

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
6 szt.
W magazynie
Zaktualizowano: 07-11-2024
Oferta od:
NLZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€48.60
net
M9F42110 product image
Schneider Electric

M9F42110

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
5 szt.
W magazynie
Zaktualizowano: 07-11-2024
Oferta od:
ESZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€55.03
net
M9F42110 product image
Schneider Electric

M9F42110

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
4 szt.
W magazynie
Zaktualizowano: 07-11-2024
Oferta od:
ITZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€62.14
net
M9F42110 product image
Schneider Electric

M9F42110

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
4 szt.
W magazynie
Zaktualizowano: 07-11-2024
Oferta od:
FRZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€90.72
net
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€8.95

Environment

Ambient Air Temperature For Operation
-30-70 °C
Tropicalisation
2 IEC 60068-1
Ip Degree Of Protection
IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree
3 EN/IEC 60947-2
Ambient Air Temperature For Storage
-40-80 °C
Relative Humidity
95-95 % 55-55 °C
Operating Altitude
0...6561.68 ft (0...2000 m)

Specifications

Line Rated Current
10 A 25 °C EN/IEC 60947-2
Curve Code
C
Number Of Protected Poles
1
Network Type
AC || DC
Standards
EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
Product Certifications
IEC || CCC || CSA || UL
Product Or Component Type
miniature circuit-breaker
Product Name
Multi9 C60
Range
Multi9
Breaking Capacity
3 kA Icu 415 V AC EN/IEC 60947-2 || 10 kA Icu 240 V AC EN/IEC 60947-2 || 20 kA Icu 60 V DC EN/IEC 60947-2 || 3 kA Icu 415 V AC GB 14048.2 || 10 kA Icu 240 V AC GB 14048.2 || 20 kA Icu 60 V DC GB 14048.2 || 10 kA AIR 277 V AC UL 489 || 14 kA AIR 240 V AC UL 489 || 14 kA AIR 120 V AC UL 489 || 10 kA AIR 60 V DC UL 489 || 10 kA AIR 277 V AC CSA C22.2 No 5 || 14 kA AIR 240 V AC CSA C22.2 No 5 || 14 kA AIR 120 V AC CSA C22.2 No 5 || 10 kA AIR 60 V DC CSA C22.2 No 5
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
1P
Device Application
distribution
Device Short Name
C60BP
Trip Unit Technology
thermal-magnetic

Complementary

[Ics] Rated Service Breaking Capacity
2.25 kA 75 % EN/IEC 60947-2 - 415 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 240 V AC || 2.25 kA 75 % GB 14048.2 - 415 V AC || 7.5 kA 75 % GB 14048.2 - 240 V AC || 15 kA 75 % GB 14048.2 - 60 V DC || 15 kA 75 % EN/IEC 60947-2 - 60 V DC
Height
103 mm
Contact Position Indicator
yes
Earth-Leakage Protection
without
Mounting Support
DIN rail
9 Mm Pitches
2
Wire Stripping Length
14 mm for top or bottom connection
Control Type
toggle
Connections - Terminals
tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 8) - rigid || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 8) - flexible with ferrule || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 8) - flexible
[Ui] Rated Insulation Voltage
500 V AC EN/IEC 60947-2
Mounting Mode
clip-on
Electrical Durability
10000 cycles
Mechanical Durability
20000 cycles
Local Signalling
ON/OFF indication
[Uimp] Rated Impulse Withstand Voltage
6 kVEN/IEC 60947-2
Color
Gray
Width
18 mm
Provision For Padlocking
padlockable
Depth
72 mm
Tightening Torque
2.5-2.5 N.m top or bottom
Magnetic Tripping Limit
8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
[Ue] Rated Operational Voltage
240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 60 V DC

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1304004EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
N/A
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free product

Modele CAD

traceparts
traceparts
Pobierz