- Network Frequency
- 60 Hz || 50 Hz
- Communication Port Support
- RS485 || ETHERNET
- Power Quality Analysis
- up to the 63rd harmonic
- Height
- 96 mm
- Measurement Voltage
- 20-400 V AC 45...65 Hz between phase and neutral || 20-828 V AC 45...65 Hz between phases
- Sampling Rate
- 128 samples/cycle
- Memory Capacity
- 1.1 MB
- Number Of Outputs
- 2 digital
- Standards
- EN 50470-1 || IEC 60529 || IEC 62053-24 || UL 61010-1 || IEC 62053-22:2020 || IEC 61557-12:2015 || EN 50470-3 || ANSI C12.20 || IEC 62053-23:2020 || IEC 62052-11:2020 || IEC 62052-31:2015
- Product Certifications
- CE IEC 61010-1 || cULus UL 61010-1 || BTL
- Type Of Measurement
- current || voltage || frequency || power factor || energy || active and reactive power
- Communication Port Protocol
- Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V || JBUS || Modbus TCP/IP 10/100 Mbit/s 2500 V || Ethernet Modbus TCP/IP daisy chain || BACnet IP || DNP3 over ethernet
- Frequency Measurement Range
- 45-65 Hz
- Ride-Through Time
- 35 ms 120 V AC typical || 129 ms 230 V AC typical || 50 ms 125 V DC typical
- Number Of Inputs
- 4 digital
- Net Weight
- 450 g
- Depth
- 72 mm
- Measurement Current
- 50-10000 mA
- Connections - Terminals
- voltage circuit screw terminal block4 || control circuit screw terminal block2 || current transformer screw terminal block6 || RS485 link screw terminal block4 || digital input screw terminal block8 || digital output screw terminal block4 || Ethernet network RJ45 connector2
- Information Displayed
- tariff 8)
- [Us] Rated Supply Voltage
- 100...300 V DC || 90...528 V AC 45...65 Hz
- Mounting Mode
- clip-on
- Measurement Accuracy
- apparent power +/- 0.5 % || frequency +/- 0.05 % || active energy +/- 0.2 % || reactive energy +/- 1 % || active power +/- 0.2 % || voltage +/- 0.1 % || power factor +/- 0.005 || current +/- 0.15 % || reactive power +/- 1 %
- Ethernet Service
- SNMP-Traps || SNTP client
- Mounting Support
- DIN rail
- Communication Gateway
- Ethernet/serial
- Poles Description
- 1P + N || 3P || 3P + N
- Data Recording
- maintenance logs || event logs || alarm logs || time stamping || data logs || min/max of instantaneous values
- Line Rated Current
- 5 A || 1 A
- Analogue Input Type
- voltage (impedance 5 MOhm) || current (impedance <= 0.3 mOhm)
- Web Services
- alarm notification by e-mail || diagnostic via predefined web pages || web server || real time viewing of data
- Width
- 96 mm
- Display Type
- Without Display
- Device Application
- power monitoring || WAGES metering || gateway || multi-tariff
- Metering Type
- measured neutral current || calculated ground current
- Accuracy Class
- class 0.2S active energy IEC 62053-22
- Maximum Power Consumption In Va
- 16 VA 480 V