- Communication Network Type
- IPv6 (internet protocol)
- Network Frequency
- 50 Hz || 60 Hz
- Communication Port Support
- ETHERNET || screw terminal block RS485
- Power Quality Analysis
- EN 50160 2010 compliance report || IEEE 519 2014 compliance report || IEC 61000-4-30 class S power quality measurement || up to the 63rd harmonic || harmonic distortion || waveform capture || voltage sag and swell detection || programmablity (logic and math functions) || IEC 62586 power quality monitoring || disturbance direction detection || rapid voltage change
- Height
- 90.5 mm
- Measurement Voltage
- 57-400 V AC 42...69 Hz between phase and neutral || 100-690 V AC 42...69 Hz between phases
- Sampling Rate
- 256 samples/cycle
- Standards
- IEC 61557-12 || IEC 62052-11 || IEC 62053-22 || IEC 62053-24 || IEEE 1588 || IEC 62586-2 || IEC 61326-1
- Memory Capacity
- 512 MB
- Number Of Outputs
- 1 pulse
- Product Certifications
- CE || cULus || N998
- Type Of Measurement
- current || voltage || frequency || active and reactive power total || apparent power total || power factor total || active and reactive power per phase, rms || apparent power per phase, rms || power factor per phase, rms
- Communication Port Protocol
- Modbus RTU 115 kbauds - 2-wire || ION 115 kbauds - 2-wire || DNP3 || IEC 61850 || Modbus TCP/IP || Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s || RSTP 801.1d 2004
- Frequency Measurement Range
- 42-69 Hz
- Communication Service
- SMTP e-mail notification || DHCP || RSTP support || NTP time synchronization || PTP time synchronization
- Power Consumption In Va
- 18 VA 415 V AC
- Number Of Inputs
- 3 digital 30 V AC || 3 digital 60 V DC
- Net Weight
- 528 g
- Depth
- 90.8 mm
- Measurement Current
- 50-10000 mA
- Information Displayed
- voltage || current || frequency || power || energy consumption || harmonic distortion
- [Us] Rated Supply Voltage
- 90...415 V AC 45...65 Hz +/- 10 % || 110...415 V DC +/- 10 %
- Mounting Mode
- clip-on
- Measurement Accuracy
- current +/- 0.1 % || voltage +/- 0.1 % || active energy +/- 0.2 %
- Mounting Support
- DIN rail
- Poles Description
- 1P + N || 3P + N || 3P
- Data Recording
- harmonics logs || sag and swell logs || GPS synchronisation || time stamping || data logs || trending/forecasting || waveform logs || alarm logs || sequence of event recording || min/max of instantaneous values || event logs || 50 data recorders
- Line Rated Current
- 1 A || 10 A || 5 A
- Cybersecurity
- password protection || port hardening || enable/disable communication ports || robust security logs || Syslog protocol support
- Isolation Voltage
- III400-690 V conforming to IEC 61010-1:ed. 3 || III400-690 V conforming to EN 61010-1:ed. 3 || III347-600 V conforming to UL 61010-1:ed. 3 || III347-600 V conforming to CSA C22.2 No 61010-1:ed. 3
- Analogue Input Type
- voltage (impedance 5 MOhm) || current (impedance 0.3 mOhm)
- Web Services
- customizable home page || file upload/download via FTP || file upload/download via SFTP || web server || alarm notification by e-mail || viewing of captured waveform (FTP) || viewing of captured waveform (web) || HTTPS server
- Width
- 90.5 mm
- Display Type
- Without Display
- Device Application
- WAGES metering || power monitoring
- Accuracy Class
- class 0.2S active energy IEC 62053-22 || class 0.2 active energy ANSI C12.20 || class 0.2 active power IEC 61557-12 || class 0.5S reactive energy IEC 62053-24 || class 0.5 power factor IEC 61557-12 || class 0.2 voltage IEC 61557-12 || class 0.2 current IEC 61557-12
- Installation Category
- III