- Network Frequency
- 50/60 Hz
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Height
- 74 mm
- Intermittent Duty Class
- 30
- [Ith] Conventional Free Air Thermal Current
- 25 A
- Mounting Support
- symmetrical rail || plate
- Network Type
- AC || DC
- [Ithe] Conventional Enclosed Thermal Current
- 20 A
- Net Weight
- 0.2 kg
- Performance Level
- high performance
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Making Capacity
- 250 A 400 V AC-21A || 250 A 400 V AC-22A || 250 A 400 V AC-23A
- Connections - Terminals
- power circuit screw clamp terminals 10-10 mm² solid || power circuit screw clamp terminals 6-6 mm² flexible - with cable end
- Contacts Type And Composition
- 3 NO
- [Icm] Rated Short-Circuit Making Capacity
- 1 kA 400 V at Ipeak
- Electrical Durability
- 100000 cycles AC-21 || 30000 cycles DC-1...5
- Suitability For Isolation
- yes
- [Ie] Rated Operational Current
- 14.5 A AC-23 Ue: 400 V
- Mechanical Durability
- 100000 cycles
- Poles Description
- 3P
- Width
- 55 mm
- Tightening Torque
- power circuit 2.1-2.1 N.m screw clamp terminals
- Depth
- 60 mm
- Breaking Capacity
- 200 A 400 V AC-21A) || 200 A 400 V AC-22A) || 200 A 400 V AC-23A)
- Rated Operational Power In W
- 11 kW 500 V AC-23A) || 11 kW 690 V AC-3) || 15 kW 690 V AC-23A) || 4 kW 230...240 V AC-3) || 5.5 kW 400...415 V AC-3) || 7.5 kW 500 V AC-3) || 5.5 kW 230...240 V AC-23A) || 7.5 kW 400...415 V AC-23A)
- Rated Conditional Short-Circuit Current
- 10 kA 400 V 25 A aM || 10 kA 400 V 25 A gG
- [Icw] Rated Short-Time Withstand Current
- 300 A 400 V 1 s